A community outbreak of Legionnaires' disease linked to hospital cooling towers: an epidemiological method to calculate dose of exposure
- PMID: 10342703
- DOI: 10.1093/ije/28.2.353
A community outbreak of Legionnaires' disease linked to hospital cooling towers: an epidemiological method to calculate dose of exposure
Abstract
Background: From July to September 1994, 29 cases of community-acquired Legionnaires' disease (LD) were reported in Delaware. The authors conducted an investigation to a) identify the source of the outbreak and risk factors for developing Legionella pneumophila serogroup 1 (Lp-1) pneumonia and b) evaluate the risk associated with the components of cumulative exposure to the source (i.e. distance from the source, frequency of exposure, and duration of exposure).
Methods: A case-control study matched 21 patients to three controls per case by known risk factors for acquiring LD. Controls were selected from patients who attended the same clinic as the respective case-patients. Water samples taken at the hospital, from eight nearby cooling towers, and from four of the patient's homes were cultured for Legionella. Isolates were subtyped using monoclonal antibody (Mab) analysis and arbitrarily primed polymerase chain reaction (AP-PCR).
Results: Eleven (52%) of 21 case-patients worked at or visited the hospital compared with 17 (27%) of 63 controls (OR 5.0, 95% CI : 1.1-29). For those who lived, worked, or visited within 4 square miles of the hospital, the risk of illness decreased by 20% for each 0.10 mile from the hospital; it increased by 80% for each visit to the hospital; and it increased by 8% for each hour spent within 0.125 miles of the hospital. Lp-1 was isolated from three patients and both hospital cooling towers. Based on laboratory results no other samples contained Lp-1. The clinical and main-tower isolates all demonstrated Mab pattern 1,2,5,6. AP-PCR matched the main-tower samples with those from two case-patients.
Conclusion: The results of our investigation suggested that the hospital cooling towers were the source of a community outbreak of LD. Increasing proximity to and frequency of exposure to the towers increased the risk of LD. New guidelines for cooling tower maintenance are needed. Knowing the location of cooling towers could facilitate maintenance inspections and outbreak investigations.
Similar articles
-
Epidemiological investigation and case-control study: a Legionnaires' disease outbreak associated with cooling towers in Warstein, Germany, August-September 2013.Euro Surveill. 2015;20(46). doi: 10.2807/1560-7917.ES.2015.20.46.30064. Euro Surveill. 2015. PMID: 26607018
-
Molecular epidemiology of an outbreak of Legionnaires' disease associated with a cooling tower in Genova-Sestri Ponente, Italy.Eur J Clin Microbiol Infect Dis. 1997 Dec;16(12):883-92. doi: 10.1007/BF01700554. Eur J Clin Microbiol Infect Dis. 1997. PMID: 9495668
-
[Community outbreak of pneumonia due to Legionella pneumophila: importance of monitoring hospital cooling towers].Enferm Infecc Microbiol Clin. 2008 Jan;26(1):15-22. Enferm Infecc Microbiol Clin. 2008. PMID: 18208761 Spanish.
-
Legionnaires' disease in France.Med Mal Infect. 2015 Mar;45(3):65-71. doi: 10.1016/j.medmal.2015.01.015. Epub 2015 Feb 24. Med Mal Infect. 2015. PMID: 25722040 Review.
-
Environmental sources of community-acquired legionnaires' disease: A review.Int J Hyg Environ Health. 2018 Jun;221(5):764-774. doi: 10.1016/j.ijheh.2018.04.013. Epub 2018 Apr 30. Int J Hyg Environ Health. 2018. PMID: 29729999 Review.
Cited by
-
Author Response to Comments on "Rolling epidemic of Legionnaires' disease outbreaks in small geographic areas".Emerg Microbes Infect. 2018 Sep 5;7(1):151. doi: 10.1038/s41426-018-0150-x. Emerg Microbes Infect. 2018. PMID: 30181566 Free PMC article. No abstract available.
-
Legionnaires' disease outbreak in Murcia, Spain.Emerg Infect Dis. 2003 Aug;9(8):915-21. doi: 10.3201/eid0908.030337. Emerg Infect Dis. 2003. PMID: 12967487 Free PMC article.
-
A large Legionnaires' disease outbreak in Pamplona, Spain: early detection, rapid control and no case fatality.Epidemiol Infect. 2008 Jun;136(6):823-32. doi: 10.1017/S0950268807009077. Epub 2007 Jul 30. Epidemiol Infect. 2008. PMID: 17662166 Free PMC article.
-
Silver as a disinfectant.Rev Environ Contam Toxicol. 2007;191:23-45. doi: 10.1007/978-0-387-69163-3_2. Rev Environ Contam Toxicol. 2007. PMID: 17708071 Free PMC article. Review.
-
Legionella longbeachae detected in an industrial cooling tower linked to a legionellosis outbreak, New Zealand, 2015; possible waterborne transmission?Epidemiol Infect. 2017 Aug;145(11):2382-2389. doi: 10.1017/S0950268817001170. Epub 2017 Jun 19. Epidemiol Infect. 2017. PMID: 28625225 Free PMC article.