Environmental allergens and irritants in schools: a focus on asthma
- PMID: 11865797
- DOI: 10.1111/j.1746-1561.2002.tb06509.x
Environmental allergens and irritants in schools: a focus on asthma
Abstract
As part of the Partners in School Asthma Management Program, environmental data were collected from 385 rooms in 60 elementary schools in southeast Texas, using an Environmental Observation Checklist and a Q-TRAK Indoor Air Quality Monitor. Dust samples for allergen analysis were collected from floors, carpets, and area rugs in 80 classrooms in a subset of 20 schools. CO2 levels > 1,000 ppm were found in 86% of rooms; 69% had indoor humidity above recommended levels. Der p I dust mite allergen levels > 2,000 ng/g were present in 20% of rooms, but only 2.5% of rooms had Der f I mite allergen levels exceeding recommended tolerances. Detectable levels of cockroach allergen (Bla g II) were found in all schools (median 5.5 ng/g), with 10% of rooms over the recommended threshold. Almost two-thirds of classrooms had mold spore counts > 10,000 col/g (median, 14,400 col/g; range, 2,000-52,000 col/g).