Legionella contamination of hospital water supplies: monitoring of private healthcare facilities in Bologna, Italy
- PMID: 11886199
- DOI: 10.1053/jhin.2002.1180
Legionella contamination of hospital water supplies: monitoring of private healthcare facilities in Bologna, Italy
Abstract
The hot water supplies of 11 private healthcare facilities in the city of Bologna, Italy, were monitored for the presence of Legionella spp. Four samplings were made in each establishment over a period of one year and in total 121 samples were collected from distribution points situated near the water-boiler and inside the wards (taps and showers). Legionellae were recovered from all the water supplies in question: Legionella spp. in 86.8% of samples, L. pneumophila in 82.6% of samples. L. pneumophila was found in all the water supplies at levels averaging above 10(4)cfu/L in five health facilities and reaching a maximum concentration of 10(7)cfu/L. The only parameter to have affected the presence of legionellae was the water temperature, which was seen to be inversely correlated to the concentration of Legionella spp. Despite the high levels of contamination from L. pneumophila, no cases of nosocomial Legionnaires' disease were reported during the period of the study.
Copyright 2002 The Hospital Infection Society.
Similar articles
-
[Legionella contamination in the hospital environment: monitoring of the hot water distribution systems of three hospitals in Catania (Italy)].Ig Sanita Pubbl. 2006 Nov-Dec;62(6):635-52. Ig Sanita Pubbl. 2006. PMID: 17256019 Italian.
-
Control of nosocomial Legionnaires' disease by keeping the circulating hot water temperature above 55 degrees C: experience from a 10-year surveillance programme in a district general hospital.J Hosp Infect. 2002 Mar;50(3):213-9. doi: 10.1053/jhin.2002.1185. J Hosp Infect. 2002. PMID: 11886198
-
[Outbreak of hospital acquired Legionnaires' disease in patients of ophthalmic ward. Nosocomial Legionella infections for the first time observed in Poland].Przegl Epidemiol. 2007;61(4):657-65. Przegl Epidemiol. 2007. PMID: 18572497 Polish.
-
[Legionella in Trondheim, Norway--determining sources of contagion and tracing risk environments].Tidsskr Nor Laegeforen. 2005 Jun 30;125(13):1791-3. Tidsskr Nor Laegeforen. 2005. PMID: 16012542 Review. Norwegian.
-
Surveillance of hospital water and primary prevention of nosocomial legionellosis: what is the evidence?J Hosp Infect. 2005 Apr;59(4):273-9. doi: 10.1016/j.jhin.2004.09.031. J Hosp Infect. 2005. PMID: 15749313 Review.
Cited by
-
Legionella contamination in hot water of Italian hotels.Appl Environ Microbiol. 2005 Oct;71(10):5805-13. doi: 10.1128/AEM.71.10.5805-5813.2005. Appl Environ Microbiol. 2005. PMID: 16204491 Free PMC article.
-
Contamination of Hospital Water Supplies in Gilan, Iran, with Legionella pneumophila, Escherichia coli, and Pseudomonas aeruginosa.Interdiscip Perspect Infect Dis. 2015;2015:809842. doi: 10.1155/2015/809842. Epub 2015 Sep 7. Interdiscip Perspect Infect Dis. 2015. Retraction in: Interdiscip Perspect Infect Dis. 2016;2016:4801509. doi: 10.1155/2016/4801509. PMID: 26448745 Free PMC article. Retracted.
-
Molecular survey of the occurrence of Legionella spp., Mycobacterium spp., Pseudomonas aeruginosa, and amoeba hosts in two chloraminated drinking water distribution systems.Appl Environ Microbiol. 2012 Sep;78(17):6285-94. doi: 10.1128/AEM.01492-12. Epub 2012 Jun 29. Appl Environ Microbiol. 2012. PMID: 22752174 Free PMC article.