A 17-month evaluation of a chlorine dioxide water treatment system to control Legionella species in a hospital water supply
- PMID: 12940577
- DOI: 10.1086/502254
A 17-month evaluation of a chlorine dioxide water treatment system to control Legionella species in a hospital water supply
Abstract
Objective: To assess the safety and efficacy of a chlorine dioxide water treatment system in controlling Legionella in a hospital water supply.
Design: For 17 months following installation of the system, we performed regular water cultures throughout the building, assessed chlorine dioxide and chlorite levels, and monitored metal corrosion.
Results: Sites that grew Legionella species decreased from 41% at baseline to 4% (P = .001). L. anisa was the only species recovered and it was found in samples of both hot and cold water. Levels of chlorine dioxide and chlorite were below Environmental Protection Agency (EPA) limits for these chemicals in potable water. Further, enhanced carbon filtration effectively removed the chemicals, even at chlorine dioxide levels of more than twice what was used to treat the water. After 9 months, corrosion of copper test strips exposed to the chlorine dioxide was not higher than that of control strips. During the evaluation period, there were no cases of nosocomial Legionella in the building with the system, whereas there was one case in another building.
Conclusions: Our results indicate that operation of a chlorine dioxide system effectively removed Legionella species from a hospital water supply. Furthermore, we found that the system was safe, as levels of chlorine dioxide and chlorite were below EPA limits. The system did not appear to cause increased corrosion of copper pipes. Our results indicate that chlorine dioxide may hold promise as a solution to the problem of Legionella contamination of hospital water supplies.
Comment in
-
Progress in the battle against nosocomial legionnaires' disease: shedding light on shades of gray.Infect Control Hosp Epidemiol. 2003 Aug;24(8):560-2. doi: 10.1086/502255. Infect Control Hosp Epidemiol. 2003. PMID: 12940574 No abstract available.
Similar articles
-
Ultraviolet light disinfection of hospital water for preventing nosocomial Legionella infection: a 13-year follow-up.Infect Control Hosp Epidemiol. 2003 Aug;24(8):580-3. doi: 10.1086/502257. Infect Control Hosp Epidemiol. 2003. PMID: 12940578
-
Safety and efficacy of chlorine dioxide for Legionella control in a hospital water system.Infect Control Hosp Epidemiol. 2007 Aug;28(8):1009-12. doi: 10.1086/518847. Epub 2007 Jun 29. Infect Control Hosp Epidemiol. 2007. PMID: 17620253
-
Experiences of the first 16 hospitals using copper-silver ionization for Legionella control: implications for the evaluation of other disinfection modalities.Infect Control Hosp Epidemiol. 2003 Aug;24(8):563-8. doi: 10.1086/502251. Infect Control Hosp Epidemiol. 2003. PMID: 12940575
-
Disinfection of water distribution systems for Legionella.Semin Respir Infect. 1998 Jun;13(2):147-59. Semin Respir Infect. 1998. PMID: 9643393 Review.
-
Hospital-acquired Legionella infections: an update on the procedures for controlling environmental contamination.Ann Ig. 2016 Mar-Apr;28(2):98-108. doi: 10.7416/ai.2016.2088. Ann Ig. 2016. PMID: 27071320 Review.
Cited by
-
Two-year evaluation of Legionella in an aging residential building: Assessment of multiple potable water remediation approaches.Sci Total Environ. 2024 Sep 1;941:173710. doi: 10.1016/j.scitotenv.2024.173710. Epub 2024 Jun 1. Sci Total Environ. 2024. PMID: 38830423
-
Two-Year Evaluation of Legionella in an Aging Residential Building: Assessment of Multiple Potable Water Remediation Approaches.medRxiv [Preprint]. 2023 Jul 23:2023.07.19.23292444. doi: 10.1101/2023.07.19.23292444. medRxiv. 2023. Update in: Sci Total Environ. 2024 Sep 1;941:173710. doi: 10.1016/j.scitotenv.2024.173710. PMID: 37502988 Free PMC article. Updated. Preprint.
-
Legionnaires' disease case-finding algorithm, attack rates, and risk factors during a residential outbreak among older adults: an environmental and cohort study.BMC Infect Dis. 2013 Jun 27;13:291. doi: 10.1186/1471-2334-13-291. BMC Infect Dis. 2013. PMID: 23806063 Free PMC article.
-
Control of Legionella Contamination and Risk of Corrosion in Hospital Water Networks following Various Disinfection Procedures.Appl Environ Microbiol. 2016 May 2;82(10):2959-2965. doi: 10.1128/AEM.03873-15. Print 2016 May 15. Appl Environ Microbiol. 2016. PMID: 26969696 Free PMC article.
Publication types
MeSH terms
Substances
LinkOut - more resources
Full Text Sources
Other Literature Sources
Medical
Research Materials