Containment testing of isolation rooms
Abstract
Results from the tracer containment testing of four 'state-of-the-art' airborne infection isolation rooms, in a new hospital, are presented. A testing technician exited an isolation room several minutes after a small quantity of tracer gas was injected over the patient bed in that room. Easily measurable tracer gas concentrations were then found in the anterooms outside the patient rooms and corridor outside the isolation room suites. Containment factors for the isolation rooms and dilution factors in the anterooms and corridor were calculated, based on the measured tracer concentrations. These results indicate the desirability of evidence-based design standards and guidelines for assessing performance of airborne infection isolation rooms. The study also demonstrates that the tracer testing procedure yields comparable results for equivalent isolation room suites, suggesting good reproducibility of the testing method.
Similar articles
-
A simple method for tracer containment testing of hospital isolation rooms.Appl Occup Environ Hyg. 2002 Jul;17(7):486-90. doi: 10.1080/10473220290035688. Appl Occup Environ Hyg. 2002. PMID: 12083168
-
Most all rooms do not follow design guidelines.Healthc Hazard Manage Monit. 2007 Nov;21(3):11-2. Healthc Hazard Manage Monit. 2007. PMID: 17993196 No abstract available.
-
Ventilation Rates and Airflow Pathways in Patient Rooms: A Case Study of Bioaerosol Containment and Removal.Ann Occup Hyg. 2015 Nov;59(9):1190-9. doi: 10.1093/annhyg/mev048. Epub 2015 Jul 17. Ann Occup Hyg. 2015. PMID: 26187326
-
Considerations on isolation rooms and alternative pressure ventilation systems.Ann Ig. 2004 Nov-Dec;16(6):777-801. Ann Ig. 2004. PMID: 15697008 Review.
-
The ventilation of multiple-bed hospital wards: review and analysis.Am J Infect Control. 2008 May;36(4):250-9. doi: 10.1016/j.ajic.2007.07.012. Am J Infect Control. 2008. PMID: 18455045 Review.
Cited by
-
Potential airborne transmission between two isolation cubicles through a shared anteroom.Build Environ. 2015 Jul;89:264-278. doi: 10.1016/j.buildenv.2015.03.004. Epub 2015 Mar 13. Build Environ. 2015. PMID: 32288029 Free PMC article.
-
Isolation anterooms: important components of airborne infection control.Am J Infect Control. 2013 May;41(5):452-5. doi: 10.1016/j.ajic.2012.06.004. Epub 2012 Oct 2. Am J Infect Control. 2013. PMID: 23036479 Free PMC article. No abstract available.
-
Impact of negative pressure system on microbiological air quality in a Central Sterile Supply Department.J Occup Health. 2021 Jan;63(1):e12234. doi: 10.1002/1348-9585.12234. J Occup Health. 2021. PMID: 33993611 Free PMC article.
-
Observing and quantifying airflows in the infection control of aerosol- and airborne-transmitted diseases: an overview of approaches.J Hosp Infect. 2011 Mar;77(3):213-22. doi: 10.1016/j.jhin.2010.09.037. Epub 2010 Dec 30. J Hosp Infect. 2011. PMID: 21194796 Free PMC article. Review.
-
Airflow patterns through single hinged and sliding doors in hospital isolation rooms - Effect of ventilation, flow differential and passage.Build Environ. 2016 Oct;107:154-168. doi: 10.1016/j.buildenv.2016.07.009. Epub 2016 Jul 15. Build Environ. 2016. PMID: 32287966 Free PMC article.