Impact of indoor air temperature and humidity in an office on perceived air quality, SBS symptoms and performance
- PMID: 15330775
- DOI: 10.1111/j.1600-0668.2004.00276.x
Impact of indoor air temperature and humidity in an office on perceived air quality, SBS symptoms and performance
Abstract
Perceived air quality (PAQ), sick building syndrome (SBS) symptoms and performance of office work were studied in a real office space at three levels of air temperature and humidity and two levels of ventilation rate (20 degrees C/40%, 23 degrees C/50%, 26 degrees C/60% RH at 10 l s(-1) p(-1) outside air, and 20 degrees C/40% RH at 3.5 l s(-1) p(-1) outside air). Thirty female subjects participated in the experiment. They were exposed to each environmental condition for 280 min. Thermal comfort was maintained at different thermal environments by self-adjustment of clothing. The subjects performed simulated office work throughout each exposure and repeatedly marked a set of visual-analog scales to indicate their perception of environmental conditions and of the intensity of SBS symptoms at the time. The study confirmed the previously observed impact of temperature and humidity on perceived air quality and the linear correlation between acceptability and enthalpy. The impact on perceived air quality of decreasing the ventilation rate from 10 to 3.5 l s(-1) per person could be counteracted by a decrement of temperature and humidity from 23 degrees C/50% RH to 20 degrees C/40% RH. Performance of office work was not significantly affected by indoor air temperature and humidity. However, several SBS symptoms were alleviated when the subjects worked at low levels of air temperature and humidity, which implies that a longer term exposure to low indoor air temperature and humidity might help to improve the performance of office work.
Practical implications: The findings of this study indicate the importance of indoor air temperature and humidity on perceived air quality and SBS symptoms. In practice, the required ventilation rate for comfort and health should no longer be independent of indoor air temperature and humidity.
Similar articles
-
Effects of thermal discomfort in an office on perceived air quality, SBS symptoms, physiological responses, and human performance.Indoor Air. 2011 Oct;21(5):376-90. doi: 10.1111/j.1600-0668.2011.00714.x. Epub 2011 Apr 18. Indoor Air. 2011. PMID: 21306437
-
Effects of pollution from personal computers on perceived air quality, SBS symptoms and productivity in offices.Indoor Air. 2004 Jun;14(3):178-87. doi: 10.1111/j.1600-0668.2004.00218.x. Indoor Air. 2004. PMID: 15104785
-
Summary of human responses to ventilation.Indoor Air. 2004;14 Suppl 7:102-18. doi: 10.1111/j.1600-0668.2004.00279.x. Indoor Air. 2004. PMID: 15330778 Review.
-
The effects of outdoor air supply rate in an office on perceived air quality, sick building syndrome (SBS) symptoms and productivity.Indoor Air. 2000 Dec;10(4):222-36. doi: 10.1034/j.1600-0668.2000.010004222.x. Indoor Air. 2000. PMID: 11089327
-
Ventilation filters and indoor air quality: a review of research from the International Centre for Indoor Environment and Energy.Indoor Air. 2004;14 Suppl 7:202-7. doi: 10.1111/j.1600-0668.2004.00289.x. Indoor Air. 2004. PMID: 15330788 Review.
Cited by
-
New considerations for representing moisture in indoor thermal conditions: Associations between enthalpy, cognitive performance, and thermal sensations.Indoor Environ. 2025 Jun;2(2):100098. doi: 10.1016/j.indenv.2025.100098. Epub 2025 May 11. Indoor Environ. 2025. PMID: 40717960 Free PMC article.
-
The impact of indoor air temperature on the executive functions of human brain and the physiological responses of body.Health Promot Perspect. 2019 Jan 23;9(1):55-64. doi: 10.15171/hpp.2019.07. eCollection 2019. Health Promot Perspect. 2019. PMID: 30788268 Free PMC article.
-
Headache symptoms and indoor environmental parameters: Results from the EPA BASE study.Ann Indian Acad Neurol. 2012 Aug;15(Suppl 1):S95-9. doi: 10.4103/0972-2327.100029. Ann Indian Acad Neurol. 2012. PMID: 23024572 Free PMC article.
-
Carbon dioxide (CO2) demand-controlled ventilation in university computer classrooms and possible effects on headache, fatigue and perceived indoor environment: an intervention study.Int Arch Occup Environ Health. 2013 Feb;86(2):199-209. doi: 10.1007/s00420-012-0756-6. Epub 2012 Mar 16. Int Arch Occup Environ Health. 2013. PMID: 22422010
-
School environment as predictor of teacher sick leave: data-linked prospective cohort study.BMC Public Health. 2012 Sep 11;12:770. doi: 10.1186/1471-2458-12-770. BMC Public Health. 2012. PMID: 22966903 Free PMC article.
Publication types
MeSH terms
LinkOut - more resources
Full Text Sources
Other Literature Sources
Medical