Mucous membrane and lower respiratory building related symptoms in relation to indoor carbon dioxide concentrations in the 100-building BASE dataset
- PMID: 15663468
- DOI: 10.1111/j.1600-0668.2004.00298.x
Mucous membrane and lower respiratory building related symptoms in relation to indoor carbon dioxide concentrations in the 100-building BASE dataset
Abstract
Indoor air pollutants are a potential cause of building related symptoms and can be reduced by increasing ventilation rates. Indoor carbon dioxide (CO(2)) concentration is an approximate surrogate for concentrations of occupant-generated pollutants and for ventilation rate per occupant. Using the US EPA 100 office-building BASE Study dataset, we conducted multivariate logistic regression analyses to quantify the relationship between indoor CO(2) concentrations (dCO(2)) and mucous membrane (MM) and lower respiratory system (LResp) building related symptoms, adjusting for age, sex, smoking status, presence of carpet in workspace, thermal exposure, relative humidity, and a marker for entrained automobile exhaust. In addition, we tested the hypothesis that certain environmentally mediated health conditions (e.g., allergies and asthma) confer increased susceptibility to building related symptoms. Adjusted odds ratios (ORs) for statistically significant, dose-dependent associations (P < 0.05) for combined mucous membrane, dry eyes, sore throat, nose/sinus congestion, sneeze, and wheeze symptoms with 100 p.p.m. increases in dCO(2) ranged from 1.1 to 1.2. Building occupants with certain environmentally mediated health conditions were more likely to report that they experience building related symptoms than those without these conditions (statistically significant ORs ranged from 1.5 to 11.1, P < 0.05).
Practical implications: These results suggest that provision of sufficient per-person outdoor ventilation air, could significantly decrease prevalence of selected building related symptoms. The observed relationship between indoor minus outdoor CO(2) concentrations and mucous membrane and lower respiratory symptoms suggests that air contaminants are implicated in the etiology of building related symptoms. Levels of indoor air pollutants that are suspected to cause building related symptoms could be reduced by increasing ventilation rates, improving ventilation effectiveness, or reducing sources of indoor air pollutants, if known.
Similar articles
-
Outdoor ozone and building-related symptoms in the BASE study.Indoor Air. 2008 Apr;18(2):156-70. doi: 10.1111/j.1600-0668.2008.00521.x. Indoor Air. 2008. PMID: 18333994
-
Indoor environmental quality in six commercial office buildings in the midwest United States.Appl Occup Environ Hyg. 2001 Nov;16(11):1065-77. doi: 10.1080/104732201753214170. Appl Occup Environ Hyg. 2001. PMID: 11757903
-
Summary of human responses to ventilation.Indoor Air. 2004;14 Suppl 7:102-18. doi: 10.1111/j.1600-0668.2004.00279.x. Indoor Air. 2004. PMID: 15330778 Review.
-
Evaluating heterogeneity in indoor and outdoor air pollution using land-use regression and constrained factor analysis.Res Rep Health Eff Inst. 2010 Dec;(152):5-80; discussion 81-91. Res Rep Health Eff Inst. 2010. PMID: 21409949
-
["Sick building syndrome"--a new problem of occupational medicine].Med Pr. 2001;52(5):369-73. Med Pr. 2001. PMID: 11828852 Review. Polish.
Cited by
-
Graphene Aerogels for In Situ Synthesis of Conductive Poly(para-phenylenediamine) Polymers, and Their Sensor Application.Micromachines (Basel). 2020 Jun 27;11(7):626. doi: 10.3390/mi11070626. Micromachines (Basel). 2020. PMID: 32605054 Free PMC article.
-
Carbon Dioxide Concentrations and Temperatures within Tour Buses under Real-Time Traffic Conditions.PLoS One. 2015 Apr 29;10(4):e0125117. doi: 10.1371/journal.pone.0125117. eCollection 2015. PLoS One. 2015. PMID: 25923722 Free PMC article.
-
Indoor humidity levels and associations with reported symptoms in office buildings.Indoor Air. 2022 Jan;32(1):e12961. doi: 10.1111/ina.12961. Epub 2021 Dec 3. Indoor Air. 2022. PMID: 34859930 Free PMC article.
-
Environmental Engineering Applications of Electronic Nose Systems Based on MOX Gas Sensors.Sensors (Basel). 2023 Jun 19;23(12):5716. doi: 10.3390/s23125716. Sensors (Basel). 2023. PMID: 37420880 Free PMC article. Review.
-
Occupant health in buildings: Impact of the COVID-19 pandemic on the opinions of building professionals and implications on research.Build Environ. 2022 Jan;207:108440. doi: 10.1016/j.buildenv.2021.108440. Epub 2021 Oct 16. Build Environ. 2022. PMID: 34697517 Free PMC article.