Efficacy of new point-of-use water filter for preventing exposure to Legionella and waterborne bacteria
Abstract
Background: Legionella species cause health care-acquired infections in which immunocompromised patients are disproportionately affected. Epidemiologic studies have demonstrated that point-of-use water fixtures are the reservoirs for these infections. The current approach to prevention is system-wide chemical disinfection of the hospital water system. These methods affect both low-risk and high-risk areas. A more effective approach to prevention may be a targeted approach aimed at protecting high-risk patients. One option is the application of a physical barrier (filter) at the point-of-use water fixture.
Objectives: To evaluate the ability of point-of-use filters to eliminate Legionella and other pathogens from water.
Methods: One hundred twenty-milliliter hot water samples were collected from 7 faucets (4 with filters and 3 without) immediately and after a 1-minute flush. Samples were collected every 2 or 3 days for 1 week. This cycle was repeated for 12 weeks. Samples were cultured for Legionella, total heterotrophic plate count (HPC) bacteria, and Mycobacterium species.
Results: Five hundred ninety-four samples were collected over 12 cycles. No Legionella or Mycobacterium were isolated from the faucets with filters between T = 0 and T = 8 days. The mean concentration of L pneumophila and Mycobacterium from the control faucets was 104.5 CFU/mL and 0.44 CFU/mL, respectively. The filters achieved a greater than 99% reduction in HPC bacteria in the immediate and postflush samples.
Conclusions: Point-of-use filters completely eliminated L pneumophila and Mycobacterium from hot water samples. These filter units could prevent exposure of high-risk patients to waterborne pathogens.
Similar articles
-
Use of terminal tap water filter systems for prevention of nosocomial legionellosis.J Hosp Infect. 2005 Jun;60(2):159-62. doi: 10.1016/j.jhin.2004.10.018. J Hosp Infect. 2005. PMID: 15866015
-
Reusable terminal tap water filters for nosocomial legionellosis prevention.Ann Hematol. 2005 Jun;84(6):403-5. doi: 10.1007/s00277-004-1000-6. Epub 2005 Feb 3. Ann Hematol. 2005. PMID: 15690178
-
Impact of a silver layer on the membrane of tap water filters on the microbiological quality of filtered water.BMC Infect Dis. 2008 Oct 8;8:133. doi: 10.1186/1471-2334-8-133. BMC Infect Dis. 2008. PMID: 18842119 Free PMC article.
-
Prevention and control of health care-associated waterborne infections in health care facilities.Am J Infect Control. 2005 Jun;33(5 Suppl 1):S26-40. doi: 10.1016/j.ajic.2005.04.002. Am J Infect Control. 2005. PMID: 15940114 Review.
-
Surveillance of hospital water and primary prevention of nosocomial legionellosis: what is the evidence?J Hosp Infect. 2005 Apr;59(4):273-9. doi: 10.1016/j.jhin.2004.09.031. J Hosp Infect. 2005. PMID: 15749313 Review.
Cited by
-
Environmental (Saprozoic) Pathogens of Engineered Water Systems: Understanding Their Ecology for Risk Assessment and Management.Pathogens. 2015 Jun 19;4(2):390-405. doi: 10.3390/pathogens4020390. Pathogens. 2015. PMID: 26102291 Free PMC article. Review.
-
Legionellosis and Recent Advances in Technologies for Legionella Control in Premise Plumbing Systems: A Review.Water (Basel). 2020 Mar 2;12(3):1-676. doi: 10.3390/w12030676. Water (Basel). 2020. PMID: 32704396 Free PMC article.
-
Legionella Risk Management and Control in Potable Water Systems: Argument for the Abolishment of Routine Testing.Int J Environ Res Public Health. 2016 Dec 24;14(1):12. doi: 10.3390/ijerph14010012. Int J Environ Res Public Health. 2016. PMID: 28029126 Free PMC article.
-
Legionella contamination of a cold-water supplying system in a German university hospital - assessment of the superheat and flush method for disinfection.J Prev Med Hyg. 2021 Sep 15;62(3):E751-E758. doi: 10.15167/2421-4248/jpmh2021.62.3.1944. eCollection 2021 Sep. J Prev Med Hyg. 2021. PMID: 34909504 Free PMC article.
-
Hygienic safety of reusable tap water filters (Germlyser) with an operating time of 4 or 8 weeks in a haematological oncology transplantation unit.BMC Infect Dis. 2007 May 23;7:45. doi: 10.1186/1471-2334-7-45. BMC Infect Dis. 2007. PMID: 17521416 Free PMC article.
Publication types
MeSH terms
LinkOut - more resources
Full Text Sources
Other Literature Sources
Medical