Role of environmental surveillance in determining the risk of hospital-acquired legionellosis: a national surveillance study with clinical correlations
- PMID: 17564984
- DOI: 10.1086/518754
Role of environmental surveillance in determining the risk of hospital-acquired legionellosis: a national surveillance study with clinical correlations
Abstract
Objective: Hospital-acquired Legionella pneumonia has a fatality rate of 28%, and the source is the water distribution system. Two prevention strategies have been advocated. One approach to prevention is clinical surveillance for disease without routine environmental monitoring. Another approach recommends environmental monitoring even in the absence of known cases of Legionella pneumonia. We determined the Legionella colonization status of water systems in hospitals to establish whether the results of environmental surveillance correlated with discovery of disease. None of these hospitals had previously experienced endemic hospital-acquired Legionella pneumonia.
Design: Cohort study.
Setting: Twenty US hospitals in 13 states.
Interventions: Hospitals performed clinical and environmental surveillance for Legionella from 2000 through 2002. All specimens were shipped to the Special Pathogens Laboratory at the Veterans Affairs Pittsburgh Medical Center.
Results: Legionella pneumophila and Legionella anisa were isolated from 14 (70%) of 20 hospital water systems. Of 676 environmental samples, 198 (29%) were positive for Legionella species. High-level colonization of the water system (30% or more of the distal outlets were positive for L. pneumophila) was demonstrated for 6 (43%) of the 14 hospitals with positive findings. L. pneumophila serogroup 1 was detected in 5 of these 6 hospitals, whereas 1 hospital was colonized with L. pneumophila serogroup 5. A total of 633 patients were evaluated for Legionella pneumonia from 12 (60%) of the 20 hospitals: 377 by urinary antigen testing and 577 by sputum culture. Hospital-acquired Legionella pneumonia was identified in 4 hospitals, all of which were hospitals with L. pneumophila serogroup 1 found in 30% or more of the distal outlets. No cases of disease due to other serogroups or species (L. anisa) were identified.
Conclusion: Environmental monitoring followed by clinical surveillance was successful in uncovering previously unrecognized cases of hospital-acquired Legionella pneumonia.
Similar articles
-
Surveillance of hospital water and primary prevention of nosocomial legionellosis: what is the evidence?J Hosp Infect. 2005 Apr;59(4):273-9. doi: 10.1016/j.jhin.2004.09.031. J Hosp Infect. 2005. PMID: 15749313 Review.
-
[The hazards of hospitals and selected public buildings of Legionella pneumophila].Pol Merkur Lekarski. 2013 Nov;35(209):263-7. Pol Merkur Lekarski. 2013. PMID: 24575645 Polish.
-
Legionella prevalence and risk of legionellosis in Hungarian hospitals.Acta Microbiol Immunol Hung. 2015 Dec;62(4):477-99. doi: 10.1556/030.62.2015.4.11. Acta Microbiol Immunol Hung. 2015. PMID: 26689882
-
Plan for the control of Legionella infections in long-term care facilities: role of environmental monitoring.Int J Hyg Environ Health. 2012 Apr;215(3):279-85. doi: 10.1016/j.ijheh.2011.08.007. Epub 2011 Sep 16. Int J Hyg Environ Health. 2012. PMID: 21925948
-
[Legionellosis--a new infection in Poland].Przegl Epidemiol. 2002;56(4):567-76. Przegl Epidemiol. 2002. PMID: 12666582 Review. Polish.
Cited by
-
Legionnaires' Disease Cases at a Large Community Hospital-Common and Underdiagnosed.Int J Environ Res Public Health. 2020 Jan 3;17(1):332. doi: 10.3390/ijerph17010332. Int J Environ Res Public Health. 2020. PMID: 31947755 Free PMC article.
-
Differential Bacterial Predation by Free-Living Amoebae May Result in Blooms of Legionella in Drinking Water Systems.Microorganisms. 2021 Jan 15;9(1):174. doi: 10.3390/microorganisms9010174. Microorganisms. 2021. PMID: 33467483 Free PMC article.
-
Molecular Typing of Legionella pneumophila Isolates in the Province of Quebec from 2005 to 2015.PLoS One. 2016 Oct 5;11(10):e0163818. doi: 10.1371/journal.pone.0163818. eCollection 2016. PLoS One. 2016. PMID: 27706210 Free PMC article.
-
Contamination of Hospital Water Supplies in Gilan, Iran, with Legionella pneumophila, Escherichia coli, and Pseudomonas aeruginosa.Interdiscip Perspect Infect Dis. 2015;2015:809842. doi: 10.1155/2015/809842. Epub 2015 Sep 7. Interdiscip Perspect Infect Dis. 2015. Retraction in: Interdiscip Perspect Infect Dis. 2016;2016:4801509. doi: 10.1155/2016/4801509. PMID: 26448745 Free PMC article. Retracted.
-
The role of water in healthcare-associated infections.Curr Opin Infect Dis. 2013 Aug;26(4):345-51. doi: 10.1097/QCO.0b013e3283630adf. Curr Opin Infect Dis. 2013. PMID: 23806897 Free PMC article. Review.
Publication types
MeSH terms
LinkOut - more resources
Full Text Sources
Other Literature Sources