Risk factors in heating, ventilating, and air-conditioning systems for occupant symptoms in US office buildings: the US EPA BASE study
- PMID: 18492050
- DOI: 10.1111/j.1600-0668.2008.00531.x
Risk factors in heating, ventilating, and air-conditioning systems for occupant symptoms in US office buildings: the US EPA BASE study
Abstract
Building-related symptoms in office workers worldwide are common, but of uncertain etiology. One cause may be contaminants related to characteristics of heating, ventilating, and air-conditioning (HVAC) systems. We analyzed data from 97 representative air-conditioned US office buildings in the Building Assessment and Survey Evaluation (BASE) study. Using logistic regression models with generalized estimating equations, we estimated odds ratios (OR) and 95% confidence intervals for associations between building-related symptom outcomes and HVAC characteristics. Outdoor air intakes less than 60 m above ground level were associated with significant increases in most symptoms: e.g. for upper respiratory symptoms, OR for intake heights 30 to 60 m, 0 to <30 m, and below ground level were 2.7, 2.0, and 2.1. Humidification systems with poor condition/maintenance were associated with significantly increased upper respiratory symptoms, eye symptoms, fatigue/difficulty concentrating, and skin symptoms, with OR = 1.5, 1.5, 1.7, and 1.6. Less frequent cleaning of cooling coils and drain pans was associated with significantly increased eye symptoms and headache, with OR = 1.7 and 1.6. Symptoms may be due to microbial exposures from poorly maintained ventilation systems and to greater levels of vehicular pollutants at air intakes nearer the ground level. Replication and explanation of these findings is needed.
Practical implications: These findings support current beliefs that moisture-related HVAC components such as cooling coils and humidification systems, when poorly maintained, may be sources of contaminants that cause adverse health effects in occupants, even if we cannot yet identify or measure the causal exposures. While finding substantially elevated risks for poorly maintained humidification systems, relative to no humidification systems, the findings do not identify important (symptom) benefits from well-maintained humidification systems. Findings also provide an initial suggestion, needing corroboration, that outdoor air intakes lower than 18 stories in office buildings may be associated with substantial increases in many symptoms. If this is corroborated and linked to ground-level vehicle emissions, urban ventilation air intakes may need to be located as far above ground level as possible or to incorporate air cleaners that remove gaseous pollutants.
Similar articles
-
Indicators of moisture and ventilation system contamination in U.S. office buildings as risk factors for respiratory and mucous membrane symptoms: analyses of the EPA BASE data.J Occup Environ Hyg. 2006 May;3(5):225-33. doi: 10.1080/15459620600628589. J Occup Environ Hyg. 2006. PMID: 16574606
-
Air filter materials, outdoor ozone and building-related symptoms in the BASE study.Indoor Air. 2008 Apr;18(2):144-55. doi: 10.1111/j.1600-0668.2008.00519.x. Indoor Air. 2008. PMID: 18333993
-
Indoor thermal factors and symptoms in office workers: findings from the US EPA BASE study.Indoor Air. 2009 Aug;19(4):291-302. doi: 10.1111/j.1600-0668.2009.00592.x. Epub 2009 Mar 13. Indoor Air. 2009. PMID: 19302503
-
Summary of human responses to ventilation.Indoor Air. 2004;14 Suppl 7:102-18. doi: 10.1111/j.1600-0668.2004.00279.x. Indoor Air. 2004. PMID: 15330778 Review.
-
Association of ventilation system type with SBS symptoms in office workers.Indoor Air. 2002 Jun;12(2):98-112. doi: 10.1034/j.1600-0668.2002.01111.x. Indoor Air. 2002. PMID: 12216473 Review.
Cited by
-
Respiratory Symptoms and Skin Sick Building Syndrome among Office Workers at University Hospital, Chiang Mai, Thailand: Associations with Indoor Air Quality, AIRMED Project.Int J Environ Res Public Health. 2022 Aug 31;19(17):10850. doi: 10.3390/ijerph191710850. Int J Environ Res Public Health. 2022. PMID: 36078565 Free PMC article.
-
Prevent or Cure-The Unprecedented Need for Self-Reporting Materials.Angew Chem Int Ed Engl. 2021 Aug 2;60(32):17290-17313. doi: 10.1002/anie.202012592. Epub 2021 Feb 26. Angew Chem Int Ed Engl. 2021. PMID: 33217121 Free PMC article. Review.
-
Towards establishing evidence-based guidelines on maximum indoor temperatures during hot weather in temperate continental climates.Temperature (Austin). 2018 May 11;6(1):11-36. doi: 10.1080/23328940.2018.1456257. eCollection 2019. Temperature (Austin). 2018. PMID: 30906809 Free PMC article. Review.
-
Disinfection of indoor air microorganisms in stack room of university library using gaseous chlorine dioxide.Environ Monit Assess. 2015 Feb;187(2):17. doi: 10.1007/s10661-014-4235-2. Epub 2015 Jan 28. Environ Monit Assess. 2015. PMID: 25626564
-
Relationship between sick building syndrome and indoor air quality among hospital staff.Med Lav. 2018 Dec 20;109(6):435-443. doi: 10.23749/mdl.v110i6.7628. Med Lav. 2018. PMID: 30556534 Free PMC article.
Publication types