Comparative Study
. 2009 Apr;19(2):122-9.
doi: 10.1111/j.1600-0668.2008.00568.x. Epub 2008 Dec 3.

Particle transport in low-energy ventilation systems. Part 1: theory of steady states

Affiliations
Comparative Study

Particle transport in low-energy ventilation systems. Part 1: theory of steady states

D T Bolster et al. Indoor Air. 2009 Apr.

Abstract

Many modern low-energy ventilation schemes, such as displacement or natural ventilation, take advantage of temperature stratification in a space, extracting the warmest air from the top of the room. The adoption of these energy-efficient ventilation systems still requires the provision of acceptable indoor air quality. In this work we study the steady state transport of particulate contaminants in a displacement-ventilated space. Representing heat sources as ideal sources of buoyancy, analytical models are developed that allow us to compare the average efficiency of contaminant removal between traditional and modern low-energy systems. We found that on average traditional and low-energy systems are similar in overall pollutant removal efficiency, although quite different vertical distributions of contaminant can exist, thus affecting individual exposure. While the main focus of this work is on particles where the dominant mode of deposition is by gravitational settling, we also discuss additional deposition mechanisms and show that the qualitative observations we make carry over to cases where such mechanisms must be included.

Practical implications: We illustrate that while average concentration of particles for traditional mixing systems and low energy displacement systems are similar, local concentrations can vary significantly with displacement systems. Depending on the source of the particles this can be better or worse in terms of occupant exposure and engineers should take due diligence accordingly when designing ventilation systems.

PubMed Disclaimer