The influence of neonatal intensive care unit design on sound level
- PMID: 20025140
- DOI: 10.1016/S1875-9572(09)60076-0
The influence of neonatal intensive care unit design on sound level
Abstract
Background: Excessive noise in nurseries has been found to cause adverse effects in infants, especially preterm infants in neonatal intensive care units (NICUs). The NICU design may influence the background sound level. We compared the sound level in two differently designed spaces in one NICU. We hypothesized that the sound level in an enclosed space would be quieter than in an open space.
Methods: Sound levels were measured continuously 24 hours a day in two separate spaces at the same time, one enclosed and one open. Sound-level meters were placed near beds in each room. Sound levels were expressed as decibels, A-weighted (dBA) and presented as hourly L(eq), L(max), L(10), and L(90).
Results: The hourly L(eq) in the open space (50.8-57.2dB) was greater than that of the enclosed space (45.9-51.7dB), with a difference of 0.4-10.4dB, and a mean difference of 4.5dB (p<0.0001). The hourly L(10), L(90), and L(max) in the open space also exceeded that in the enclosed space (p<0.0001).
Conclusion: The sound level measured in the enclosed space was quieter than in the open space. The design of bed space should be taken into consideration when building a new NICU. Besides the design of NICU architecture, continuous monitoring of sound level in the NICU is important to maintain a quiet environment.
Similar articles
-
Comparing sound measurements in the single-family room with open-unit design neonatal intensive care unit: the impact of equipment noise.J Perinatol. 2012 May;32(5):368-73. doi: 10.1038/jp.2011.103. Epub 2011 Aug 18. J Perinatol. 2012. PMID: 21852773
-
Planning the acoustic environment of a neonatal intensive care unit.Clin Perinatol. 2004 Jun;31(2):331-52, viii. doi: 10.1016/j.clp.2004.04.014. Clin Perinatol. 2004. PMID: 15289037 Review.
-
A descriptive study of noise in the neonatal intensive care unit. Ambient levels and perceptions of contributing factors.Adv Neonatal Care. 2008 Jun;8(3):165-75. doi: 10.1097/01.ANC.0000324341.24841.6e. Adv Neonatal Care. 2008. PMID: 18535422
-
A Comparison of Sound Levels in Open Plan Versus Pods in a Neonatal Intensive Care Unit.HERD. 2017 Apr;10(3):30-39. doi: 10.1177/1937586716668636. Epub 2016 Sep 28. HERD. 2017. PMID: 27682021
-
Evidence-based design for infants and staff in the neonatal intensive care unit.Clin Perinatol. 2004 Jun;31(2):299-311, vii. doi: 10.1016/j.clp.2004.04.005. Clin Perinatol. 2004. PMID: 15289034 Review.
Cited by
-
Intensive Care Unit Built Environments: A Comprehensive Literature Review (2005-2020).HERD. 2021 Oct;14(4):368-415. doi: 10.1177/19375867211009273. Epub 2021 May 18. HERD. 2021. PMID: 34000842 Free PMC article. Review.
-
Newborn Incubators Do Not Protect from High Noise Levels in the Neonatal Intensive Care Unit and Are Relevant Noise Sources by Themselves.Children (Basel). 2021 Aug 16;8(8):704. doi: 10.3390/children8080704. Children (Basel). 2021. PMID: 34438595 Free PMC article.
-
Evidence-based design for neonatal units: a systematic review.Matern Health Neonatol Perinatol. 2019 Apr 30;5:6. doi: 10.1186/s40748-019-0101-0. eCollection 2019. Matern Health Neonatol Perinatol. 2019. PMID: 31061714 Free PMC article. Review.
-
Safe sound exposure in the fetus and preterm infant.J Obstet Gynecol Neonatal Nurs. 2012 Mar;41(2):166-170. doi: 10.1111/j.1552-6909.2012.01342.x. J Obstet Gynecol Neonatal Nurs. 2012. PMID: 22834845 Free PMC article. Review.
-
Mother's voice and heartbeat sounds elicit auditory plasticity in the human brain before full gestation.Proc Natl Acad Sci U S A. 2015 Mar 10;112(10):3152-7. doi: 10.1073/pnas.1414924112. Epub 2015 Feb 23. Proc Natl Acad Sci U S A. 2015. PMID: 25713382 Free PMC article.