The role of exhaust ventilation systems in reducing occupational exposure to organic solvents in a paint manufacturing factory
- PMID: 20040984
- PMCID: PMC2796753
- DOI: 10.4103/0019-5278.43266
The role of exhaust ventilation systems in reducing occupational exposure to organic solvents in a paint manufacturing factory
Abstract
This paper presents the successful design and implementation of several exhaust ventilation systems in a paint manufacturing factory. The ventilation systems were designed based on American Conference of Governmental Industrial Hygienists recommendations. The duct works, fans, and other parts were made and mounted by local manufacturers. The concentrations of toluene and xylene as the common solvents used in paint mixing factories were measured to evaluate the role of ventilation systems in controlling the organic solvents. Occupational exposure to toluene and xylene as the major pollutants was assessed with and without applying ventilation systems. For this purpose, samples were taken from breathing zone of exposed workers using personal samples. The samples were analyzed using Occupational Safety and Health Administration analytical method No.12. The samples were quantified using gas chromatography. The results showed that the ventilation systems successfully controlled toluene and xylene vapors in workplace, air well below the recommended threshold limit value of Iran (44.49 and 97.73 ppm, respectively). It was also discovered that benzene concentration in workplace air was higher than its allowable concentrations. This could be from solvents impurities that require more investigations.
Keywords: Exhaust ventilation systems; occupational exposure; paint manufacturing; ventilation standard.
Conflict of interest statement
Figures










References
-
- Ridgwaya P, Nixon TE, Leach JP. Occupational exposure to organic solvents and long-term nervous system damage detectable by brain imaging, neurophysiology or histopathology. Food Chem Toxicol. 2003;41:153–87. - PubMed
-
- NIOSH, Occupational Diseases - A Guide to their Recognition, in Publication No 77-181. 1977.
-
- Williams PR, Knutsen JS, Atkinson C, Madl AK, Paustenbach DJ. Airborne concentrations of benzene associated with the historical use of some formulations of liquid wrench. J Occup Environ Hyg. 2007;4(8):547–561. - PubMed
-
- McMinn BW. Control of VOC emissions from ink and paint manufacturing processes. C.T. Center. Environmental Protection Agency. 1992.
-
- ACGIH, Industrial Ventilation a manual of recommended practice. 22 ed. ACGIH; 1995.