Occupational exposure to electric and magnetic fields during work tasks at 110 kV substations in the Tampere region
- PMID: 20077529
- DOI: 10.1002/bem.20555
Occupational exposure to electric and magnetic fields during work tasks at 110 kV substations in the Tampere region
Abstract
The occupational exposure to electric and magnetic fields during various work tasks at seven 110 kV substations in Finland's Tampere region was studied. The aim was to investigate if the action values (10 kV/m for the E-field and 500 microT for the B-field) of the EU Directive 2004/40/EC were exceeded. Electric and magnetic fields were measured during the following work tasks: (1) walking or operating devices on the ground; (2) working from a service platform; (3) working around the power transformer on the ground or using a ladder; and (4) changing a bulb from a man hoist. In work task 2 "working from a service platform" the measured electric field (maximum value 16.6 kV/m) exceeded 10 kV/m in three cases. In the future it is important to study if the limit value (10 mA/m(2)) of Directive 2004/40/EC is exceeded at 110 kV substations. The occupational 500 microT action value of the magnetic flux density field (B-field) was not exceeded in any working situation.
Similar articles
-
Occupational exposure to electric and magnetic fields while working at switching and transforming stations of 110 kV.Ann Occup Hyg. 2011 Jun;55(5):526-36. doi: 10.1093/annhyg/mer013. Epub 2011 Mar 30. Ann Occup Hyg. 2011. PMID: 21454328
-
Occupational exposure to electric fields and currents associated with 110 kV substation tasks.Bioelectromagnetics. 2012 Jul;33(5):438-42. doi: 10.1002/bem.21711. Epub 2012 Feb 14. Bioelectromagnetics. 2012. PMID: 22334373
-
Occupational exposure to electric and magnetic fields during tasks at ground or floor level at 110 kV substations in Finland.Int J Occup Saf Ergon. 2016 Sep;22(3):384-8. doi: 10.1080/10803548.2016.1153858. Epub 2016 Apr 14. Int J Occup Saf Ergon. 2016. PMID: 27075421 Free PMC article.
-
[Evaluation of reports on environmental measurements of electromagnetic fields generated by high voltage transmission lines and substations].Med Pr. 2007;58(2):169-75. Med Pr. 2007. PMID: 17926507 Review. Polish.
-