Environmental surveillance of Legionella pneumophila in two Italian hospitals
- PMID: 20847460
- DOI: 10.4415/ANN_10_03_08
Environmental surveillance of Legionella pneumophila in two Italian hospitals
Abstract
The aim of this study was to identify the most effective disinfection protocol to reduce the presence of Legionella pneumophila in the water system of two Italian hospitals. From 2004 to 2009, 271 samplings of hot water were carried out in 11 hospital units to detect the presence of L. pneumophila. Additionally, water samples collected from one boiler outlet and the hot water recirculation were tested. From 2004 to 2009, L. pneumophila was present in 37% of the samples. Of these, 68.3% and 18.8% were positive for serogroups 2-14 and 1, respectively. Furthermore, 12.9% of the samples were positive for both serogroups. Finally, a maximal count of 10(4) CFU/L was measured in the most distal sites. To reduce L. pneumophila colonization, a two-year long hyperchlorination (2004-2006) was carried out. Moreover, from June 2005 until now, continuous maintenance of boilers and tanks, substitution of the shower heads and increase of the boiler outlet temperature to 60 °C were performed. All these treatments led to a marked reduction of L. pneumophila colonization in the short but not in the medium-long term. Only the use of chlorine dioxide led, after four years, to a reduction of the loads of L. pneumophila to values below 100 CFU/L. However, in the distal sites a persistent degree of colonization (maximum value 700 CFU/L, average 600 CFU/L) was observed probably due to the presence of L. pneumophila in the stagnant water in dead legs. In conclusion, data show that long-term chlorination of hot water sources together with carefully aimed maintenance of water pipes can lead to an effective reduction of L. pneumophila concentration in hospital water systems.
Similar articles
-
[5-year surveillance for Legionella pneumophila and comparison of disinfection methods in two hospitals of Milan].Ann Ig. 2007 Nov-Dec;19(6):533-40. Ann Ig. 2007. PMID: 18376574 Italian.
-
Hospital characteristics associated with colonization of water systems by Legionella and risk of nosocomial legionnaires' disease: a cohort study of 15 hospitals.Infect Control Hosp Epidemiol. 1999 Dec;20(12):798-805. doi: 10.1086/501587. Infect Control Hosp Epidemiol. 1999. PMID: 10614602
-
[The hazards of hospitals and selected public buildings of Legionella pneumophila].Pol Merkur Lekarski. 2013 Nov;35(209):263-7. Pol Merkur Lekarski. 2013. PMID: 24575645 Polish.
-
Disinfection of water distribution systems for Legionella.Semin Respir Infect. 1998 Jun;13(2):147-59. Semin Respir Infect. 1998. PMID: 9643393 Review.
-
Prevention of Legionnaires' disease in hospitals.Tidsskr Nor Laegeforen. 2011 Aug 23;131(16):1554-7. doi: 10.4045/tidsskr.09.0881. Tidsskr Nor Laegeforen. 2011. PMID: 21866196 Review. English, Norwegian.
Cited by
-
Environmental surveillance of Legionella pneumophila in distal water supplies of a hospital for early identification & prevention of hospital-acquired legionellosis.Indian J Med Res. 2018 Jun;147(6):611-614. doi: 10.4103/ijmr.IJMR_527_17. Indian J Med Res. 2018. PMID: 30168494 Free PMC article.
-
Environmental surveillance and molecular epidemiology of waterborne pathogen Legionella pneumophila in health-care facilities of Northeastern Greece: a 4-year survey.Environ Sci Pollut Res Int. 2015 May;22(10):7628-40. doi: 10.1007/s11356-014-3740-8. Epub 2015 Feb 25. Environ Sci Pollut Res Int. 2015. PMID: 25712880
-
Prevalence of Legionella in a Public Building Water Plumbing System During COVID-19 Lockdown.Environ Health (Wash). 2023 Oct 4;1(5):352-359. doi: 10.1021/envhealth.3c00058. eCollection 2023 Nov 17. Environ Health (Wash). 2023. PMID: 39474278 Free PMC article.
-
Control of Legionella Contamination and Risk of Corrosion in Hospital Water Networks following Various Disinfection Procedures.Appl Environ Microbiol. 2016 May 2;82(10):2959-2965. doi: 10.1128/AEM.03873-15. Print 2016 May 15. Appl Environ Microbiol. 2016. PMID: 26969696 Free PMC article.
-
The Detection Limits of Legionella According to the EU Directive 2020/2184. Could That Be Too Permissive?Adv Exp Med Biol. 2025;1476:23-30. doi: 10.1007/5584_2023_790. Adv Exp Med Biol. 2025. PMID: 37777698