Experimental study of airflow characteristics of stratum ventilation in a multi-occupant room with comparison to mixing ventilation and displacement ventilation
- PMID: 25626596
- DOI: 10.1111/ina.12188
Experimental study of airflow characteristics of stratum ventilation in a multi-occupant room with comparison to mixing ventilation and displacement ventilation
Abstract
The motivation of this study is stimulated by a lack of knowledge about the difference of airflow characteristics between a novel air distribution method [i.e., stratum ventilation (SV)] and conventional air distribution methods [i.e., mixing ventilation (MV) and displacement ventilation (DV)]. Detailed air velocity and temperature measurements were conducted in the occupied zone of a classroom with dimensions of 8.8 m (L) × 6.1 m (W) × 2.4 m (H). Turbulence intensity and power spectrum of velocity fluctuation were calculated using the measured data. Thermal comfort and cooling efficiency were also compared. The results show that in the occupied zone, the airflow characteristics among MV, DV, and SV are different. The turbulent airflow fluctuation is enhanced in this classroom with multiple thermal manikins due to thermal buoyancy and airflow mixing effect. Thermal comfort evaluations indicate that in comparison with MV and DV, a higher supply air temperature should be adopted for SV to achieve general thermal comfort with low draft risk. Comparison of the mean air temperatures in the occupied zone reveals that SV is of highest cooling efficiency, followed by DV and then MV.
Practical implications: This study reports the unique profiles of flow, temperature, turbulence intensity, and power spectrum of stratum ventilation, which can have a number of implications for both knowledge and understanding of the flow characteristics in a stratum-ventilated room. With respect to the former, it expounds the fundamental characteristics of this air distribution method; and with respect to the latter, it reveals the mechanism of thermal comfort and energy saving under stratum ventilation.
Keywords: Air distribution; Airflow; Energy saving; Power spectrum; Stratum ventilation; Thermal comfort; Turbulence intensity.
© 2015 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.
Similar articles
-
Evaluation of thermal comfort conditions in a classroom with three ventilation methods.Indoor Air. 2011 Jun;21(3):231-9. doi: 10.1111/j.1600-0668.2010.00693.x. Epub 2011 Jan 25. Indoor Air. 2011. PMID: 21204985
-
Experimental investigation into the interaction between the human body and room airflow and its effect on thermal comfort under stratum ventilation.Indoor Air. 2016 Apr;26(2):274-85. doi: 10.1111/ina.12208. Epub 2015 Apr 27. Indoor Air. 2016. PMID: 25857272
-
Uniformity of stratum-ventilated thermal environment and thermal sensation.Indoor Air. 2014 Oct;24(5):521-32. doi: 10.1111/ina.12097. Epub 2014 Mar 17. Indoor Air. 2014. PMID: 24438214
-
Personalized ventilation.Indoor Air. 2004;14 Suppl 7:157-67. doi: 10.1111/j.1600-0668.2004.00284.x. Indoor Air. 2004. PMID: 15330783 Review.
-
Breathing thermal manikins for indoor environment assessment: important characteristics and requirements.Eur J Appl Physiol. 2004 Sep;92(6):710-3. doi: 10.1007/s00421-004-1142-1. Eur J Appl Physiol. 2004. PMID: 15168126 Review.
Cited by
-
Experimental study on the control effect of different ventilation systems on fine particles in a simulated hospital ward.Sustain Cities Soc. 2021 Oct;73:103102. doi: 10.1016/j.scs.2021.103102. Epub 2021 Jun 17. Sustain Cities Soc. 2021. PMID: 34189016 Free PMC article.
-
Contaminant removal and contaminant dispersion of air distribution for overall and local airborne infection risk controls.Sci Total Environ. 2022 Aug 10;833:155173. doi: 10.1016/j.scitotenv.2022.155173. Epub 2022 Apr 11. Sci Total Environ. 2022. PMID: 35421454 Free PMC article.
-
Study on the impact of parallel jet spacing on the performance of multi-jet stratum ventilation.Appl Energy. 2022 Jan 15;306:118135. doi: 10.1016/j.apenergy.2021.118135. Epub 2021 Nov 9. Appl Energy. 2022. PMID: 34776588 Free PMC article.
-
Effects of Evaporative Cooling Air Conditioning on Classroom Pollutants and Thermal Environment.Environ Health Insights. 2022 Jul 23;16:11786302221113995. doi: 10.1177/11786302221113995. eCollection 2022. Environ Health Insights. 2022. PMID: 35899225 Free PMC article.
-
Integrated system of exhaust air heat pump and advanced air distribution for energy-efficient provision of outdoor air.Appl Therm Eng. 2022 Nov 25;217:119256. doi: 10.1016/j.applthermaleng.2022.119256. Epub 2022 Sep 3. Appl Therm Eng. 2022. PMID: 36091098 Free PMC article.
Publication types
MeSH terms
LinkOut - more resources
Full Text Sources
Medical