Legionellosis Outbreak Associated With a Hotel Fountain
- PMID: 26716104
- PMCID: PMC4692259
- DOI: 10.1093/ofid/ofv164
Legionellosis Outbreak Associated With a Hotel Fountain
Abstract
Background. In August 2012, the Chicago Department of Public Health (CDPH) was notified of acute respiratory illness, including 1 fatality, among a group of meeting attendees who stayed at a Chicago hotel during July 30-August 3, 2012. Suspecting Legionnaires' disease (LD), CDPH advised the hotel to close their swimming pool, spa, and decorative lobby fountain and began an investigation. Methods. Case finding included notification of individuals potentially exposed during July 16-August 15, 2012. Individuals were interviewed using a standardized questionnaire. An environmental assessment was performed. Results. One hundred fourteen cases were identified: 11 confirmed LD, 29 suspect LD, and 74 Pontiac fever cases. Illness onsets occurred July 21-August 22, 2012. Median age was 48 years (range, 22-82 years), 64% were male, 59% sought medical care (15 hospitalizations), and 3 died. Relative risks for hotel exposures revealed that persons who spent time near the decorative fountain or bar, both located in the lobby were respectively 2.13 (95%, 1.64-2.77) and 1.25 (95% CI, 1.09-1.44) times more likely to become ill than those who did not. Legionella pneumophila serogroup 1 was isolated from samples collected from the fountain, spa, and women's locker room fixtures. Legionella pneumophila serogroup 1 environmental isolates and a clinical isolate had matching sequence-based types. Hotel maintenance records lacked a record of regular cleaning and disinfection of the fountain. Conclusions. Environmental testing identified Legionella in the hotel's potable water system. Epidemiologic and laboratory data indicated the decorative fountain as the source. Poor fountain maintenance likely created favorable conditions for Legionella overgrowth.
Keywords: Pontiac fever; fountain outbreak; legionellosis.
Figures
References
-
- Centers for Disease Control and Prevention (CDC). Legionellosis—United States, 2000–2009. MMWR Morb Mortal Wkly Rep 2011; 60:1083–6. - PubMed
-
- Benin AL, Benson RF, Arnold KE et al. . An outbreak of travel-associated Legionnaires’ disease and Pontiac fever: the need for enhanced surveillance of travel-associated legionellosis in the United States. J Infect Dis 2002; 185:237–43. - PubMed
-
- Euser SM, Pelgrim M, Den Boer JW. Legionnaires’ disease and Pontiac fever after using a private outdoor whirlpool spa. Scand J Infect Dis 2010; 42:910–6. - PubMed
-
- Haupt TE, Heffernan RT, Kazmierczak JJ et al. . An outbreak of Legionnaires disease associated with a decorative water wall fountain in a hospital. Infect Control Hosp Epidemiol 2013; 33:185–91. - PubMed
-
- Ng V, Tang P, Fisman DN. Our evolving understanding of legionellosis epidemiology: learning to count. Clin Infect Dis 2008; 47:600–2. - PubMed
LinkOut - more resources
Full Text Sources
Other Literature Sources
Research Materials