Skip to main page content
U.S. flag

An official website of the United States government

Dot gov

The .gov means it’s official.
Federal government websites often end in .gov or .mil. Before sharing sensitive information, make sure you’re on a federal government site.

Https

The site is secure.
The https:// ensures that you are connecting to the official website and that any information you provide is encrypted and transmitted securely.

Access keys NCBI Homepage MyNCBI Homepage Main Content Main Navigation
. 2018 Mar 1;57(2):138-142.

Evaluation of Extended Sanitation Interval for Cage Top Components in Individually Ventilated Mouse Cages

Affiliations

Evaluation of Extended Sanitation Interval for Cage Top Components in Individually Ventilated Mouse Cages

Brianne Ls Ball et al. J Am Assoc Lab Anim Sci. .

Abstract

Sanitation frequency of mouse cage components can be determined through verification of microenvironment, including microbiologic load and air quality within the cage. Here we demonstrate a consistent microbiologic load on wire IVC lids that were used for as long as 8 continuous weeks to house 4 or 5 mice and significant decreases in the microbial load on filter tops at 4, 6, and 8 wk compared with 2 wk. In addition, air quality, represented by intracage ammonia concentration at the time of bedding change, did not differ between 2-, 4-, and 6-wk time points in cages containing same-sex groups of 4 or 5 male or female adult mice. We propose that the lack of significant differences represents justification for an extended sanitation frequency of as long as 6 wk for cage top components in mouse IVC housing and represents a performance standard that might be reproduced by similar facilities to determine appropriate sanitation frequencies for mouse caging components.

PubMed Disclaimer

Figures

Figure 1.
Figure 1.
Design and air movement in the IVC used in the current study. These IVC have HEPA-filtered air supplied through sealed shelf plenums into the cage, through air supply ports above the cage filter top. Air enters through the rear of the cage and exits at the front of the plenum. Water valves are located at the back of the shelf and enter the cage approximately 3.5 in. above the plastic floor through a manufacturer-installed grommet. This grommet is covered by a hinged door when not in use and is the access point for ammonia testing.
Figure 2.
Figure 2.
Locations of microbiologic sampling points. Two 4 × 4-cm squares of the inner face of the filter top (sites A and B) and two 4-cm lengths of 5 bars of the wire lid (sites C and D) were sampled.
Figure 3.
Figure 3.
Microbial load (no. of cfu) on cage top components. The median (point) and middle quartiles (bars) of each data set are indicated for each sample location (sites A, B, C, and D) across the 4 time points (2, 4, 6, and 8 wk). Significant differences were identified only for sample A, between the 2-wk time point and each of the other time points. P values as measured by Friedman testing are indicated where significance was identified.

Similar articles

Cited by

References

    1. AAALAC International. [Internet] 2017. AAALAC: accreditation FAQ D2. [Cited 14 September 2017]. Available at: https://www.aaalac.org/accreditation/faq_landing.cfm#C1
    1. Creamer MA, Petty J, Martin T, Bergdall V, Hickman-Davis JM. 2014. Implications of natural occlusion of ventilated racks on ammonia and sanitation practices. J Am Assoc Lab Anim Sci 53:174–179. - PMC - PubMed
    1. Ferrecchia CE, Jensen K, Van Andel R. 2014. Intracage ammonia levels in static and individually ventilated cages housing C57BL/6 mice on 4 bedding substrates. J Am Assoc Lab Anim Sci 53: 146–151. - PMC - PubMed
    1. Fox JG, Barthold S, Davisson M, Newcomer C, Quimby F, Smith A. 2007. The mouse in biomedical research. Burlington (MA): Elsevier.
    1. Godbey T, Gray G, Jeffery D. 2011. Cage-change interval preference in mice. Lab Anim (NY) 40:225–230. - PubMed

LinkOut - more resources