Concentration and type of bioaerosols before and after conventional disinfection and sterilization procedures inside hospital operating rooms

Affiliations

Concentration and type of bioaerosols before and after conventional disinfection and sterilization procedures inside hospital operating rooms

Mansooreh Dehghani et al. Ecotoxicol Environ Saf. .

Abstract

Operating rooms (ORs) in hospitals are sensitive wards because patients can get infections. This work aimed to characterize the type and concentration of bioaerosols in nine ORs of an educational hospital before and after sterilization and disinfection. During 2017, fungal samples were incubated at 25-28 °C for 3-7 days and bacterial samples at 37 °C for 24-48 h. The study results showed that the concentrations of fungi before cleaning procedures (for both of disinfection and sterilization) were limited from 4.83 to 18.40 CFU/m3 and after cleaning procedures ranged from 1.90 to 8.90 CFU/m3. In addition, the concentrations of bacteria before cleaning procedures were limited 14.65-167.40 CFU/m3 and after cleaning procedures ranged from 9.50 to 38.40 CFU/m3. The difference between the mean concentrations of airborne bioaerosols before and after sterilization was significantly different than the suggested value of 30 CFU/m3 (p ≤ 0.05). The bacterial concentration was higher than the recommended value (30 CFU/m3) in 41% of the ORs. The main fungal species identified in the indoor air of ORs (before vs. after sterilization) were A. fumigatus (25.6 vs. 18.3%), A. Niger (11.6 vs. 5.8%), Penicillium spp. (5.5 vs. 3.3%), Alternaria spp. (2.8 vs. 0.7%), Fusarium spp. (9.7 vs. 3.7%), Mucor spp. (15 vs. 12.7%), Cephalotrichum spp. (1.7 vs. 0.8%), A. Flavus (24.6 vs. 18.5%), Cladosporium spp. (2.6 vs. 0.8%), and Trichoderma spp. (0 vs. 0.9%). The growth of biological species even after sterilization and disinfection likely resulted from factors including poor ventilation, sweeping of OR floors, inadequate HVAC filtration, high humidity, and also lack of optimum management of infectious waste after surgery. Designing well-constructed ventilation and air-conditioning systems, replacing HEPA filters, implementing more stringent, frequent, and comprehensive disinfection procedures, and controlling temperature and humidity can help decrease bioaerosols in ORs.

Keywords: Bioaerosol; Indoor air; Operating room; Shiraz; Sterilization.

PubMed Disclaimer

Conflict of interest statement

Competing interest

“The authors declare that they have no competing interests.”

Figures

Fig. 1.
Fig. 1.
Map of Iran and Shiraz indicating the location of the selected hospital.
Fig. 2.
Fig. 2.
The mean ± SD of bacteria in indoor air of ORs before and after disinfection and sterilization.
Fig. 3.
Fig. 3.
The average ± SD of fungi in indoor air of ORs before and after disinfection and sterilization.
Fig. 4.
Fig. 4.
The percentage of fungi and fungi genera in indoor air of ORs before (left) and after (right) disinfection and sterilization.

Similar articles

Cited by

References

    1. Ammann H, 1998. Why ACGIH Bioaerosol Committee does not recommend TLVs for bioaerosols. In: Proceedings of the Third International Conference on Bioaerosols, Fungi and Mycotoxins: Health Effects, Assessment, Prevention and Control, pp. 23–25.
    1. Audurier A, et al., 1985. Bacterial contamination of the air in different operating rooms.Rev. D.’Epidemiol. Et. De. Sante Publique 33, 134–141. - PubMed
    1. Azimi F, et al., 2013. Fungal air quality in hospital rooms: a case study in Tehran, Iran. J. Environ. Health Sci. Eng 11, 30. - PMC - PubMed
    1. Brown AE, Benson HJ, 2004. Benson’s microbiological applications: laboratory manual in general microbiology, Short Version. McGraw-Hill Science, Engineering & Mathematics.
    1. Chow T, Yang X, 2005. Ventilation performance in the operating theatre against airborne infection: numerical study on an ultra-clean system. J. Hosp. Infect 59, 138–147. - PubMed