Potential airborne pathogen transmission in a hospital with and without surge control ventilation system modifications
- PMID: 32287965
- PMCID: PMC7116960
- DOI: 10.1016/j.buildenv.2016.06.029
Potential airborne pathogen transmission in a hospital with and without surge control ventilation system modifications
Abstract
To better understand the transport of airborne particulate matter (PM) in hospital environments when surge control strategies are implemented, tests were conducted in a recently decommissioned hospital during a one-week period. An aerosol was released within a patient room and concentrations measured in the room and hallway with and without surge control ventilation system modifications. The average hallway protection efficiencies were high (>98%) both for the baseline ventilation configuration and when the ventilation system was modified for whole floor negative pressure, indicating very little PM reached the hallway. During entry/exit events through the patient room door into the hallway, the average minimum hallway protection efficiencies were lower during the modified ventilation operation (93-94%) than for the baseline operation (98-99%). These lower hallway protection efficiencies may be explained by the 52% reduction in the outdoor air ventilation being supplied to the hallway during the modified operation mode. This suggests that patient room doors should remain closed to control PM movement into the hallway. In addition, if there is concern about airborne infection transmission, an anteroom may be used to further reduce the transport of particles from the patient rooms to the hallways of the ward.
Keywords: Aerosol; Infectious disease; Negative pressure.
© 2016 Elsevier Ltd. All rights reserved.
Figures


References
-
- Adams N.J., Lynch R.A., Mead K.R. The effect of pressure differential and care provider movement on airborne infectious isolation room containment effectiveness. Am. J. Infect. Control. 2011;39:91–97. - PubMed
-
- ASHRAE . American Society of Heating, Refrigerating and Air–Conditioning Engineers, Inc.; Atlanta, GA: 2007. Standard 52.2–2007, Method of Testing General Ventilation Air-cleaning Devices for Removal Efficiency by Particle Size.
-
- ASHRAE . American Society of Heating, Refrigerating and Air–Conditioning Engineers, Inc.; Atlanta, GA: 2013. Standard 170–2013, Ventilation of Health Care Facilities.
-
- Centers for Disease Control and Prevention . January 2004. Public Health Guidance for Community-level Preparedness and Response to Severe Acute Respiratory Syndrome (SARS) Version 2 — Supplement I: Infection Control in Healthcare, Home, and Community Settings.http://www.cdc.gov/sars/guidance/I-infection/healthcare.pdf Available at: accessed 23.05.16.
-
- Centers for Disease Control and Prevention . Idem; September 2013. Interim Infection Prevention and Control Recommendations for Hospitalized Patients with Middle East Respiratory Syndrome Coronavirus (MERS-CoV)http://www.cdc.gov/coronavirus/mers/infection-prevention-control.html Available at: accessed 23.05.16.
LinkOut - more resources
Full Text Sources