How Molecular Typing Can Support Legionella Environmental Surveillance in Hot Water Distribution Systems: A Hospital Experience
- PMID: 33233464
- PMCID: PMC7700474
- DOI: 10.3390/ijerph17228662
How Molecular Typing Can Support Legionella Environmental Surveillance in Hot Water Distribution Systems: A Hospital Experience
Abstract
In this study, we aimed to associate the molecular typing of Legionella isolates with a culture technique during routine Legionella hospital environmental surveillance in hot water distribution systems (HWDSs) to develop a risk map able to be used to prevent nosocomial infections and formulate appropriate preventive measures. Hot water samples were cultured according to ISO 11731:2017. The isolates were serotyped using an agglutination test and genotyped by sequence-based typing (SBT) for Legionella pneumophila or macrophage infectivity potentiator (mip) gene sequencing for non-pneumophila Legionella species. The isolates' relationship was phylogenetically analyzed. The Legionella distribution and level of contamination were studied in relation to temperature and disinfectant residues. The culture technique detected 62.21% of Legionella positive samples, characterized by L. pneumophila serogroup 1, Legionella non-pneumophila, or both simultaneously. The SBT assigned two sequence types (STs): ST1, the most prevalent in Italy, and ST104, which had never been isolated before. The mip gene sequencing detected L. anisa and L. rubrilucens. The phylogenetic analysis showed distinct clusters for each species. The distribution of Legionella isolates showed significant differences between buildings, with a negative correlation between the measured level of contamination, disinfectant, and temperature. The Legionella molecular approach introduced in HWDSs environmental surveillance permits (i) a risk map to be outlined that can help formulate appropriate disinfection strategies and (ii) rapid epidemiological investigations to quickly identify the source of Legionella infections.
Keywords: Legionella pneumophila; culture technique; disinfection treatment; macrophage infectivity potentiator (mip) sequencing; non-pneumophila Legionella species; sequence types (STs); sequence-based typing (SBT); water safety plan.
Conflict of interest statement
The authors declare no conflict of interest.
Figures
Similar articles
-
Identification of Legionella pneumophila serogroups and other Legionella species by mip gene sequencing.J Infect Chemother. 2012 Apr;18(2):276-81. doi: 10.1007/s10156-011-0324-0. Epub 2011 Oct 21. J Infect Chemother. 2012. PMID: 22015397
-
Molecular typing of Legionella pneumophila from air-conditioning cooling waters using mip gene, SBT, and FAFLP methods.J Microbiol Methods. 2017 Aug;139:1-7. doi: 10.1016/j.mimet.2017.04.002. Epub 2017 Apr 7. J Microbiol Methods. 2017. PMID: 28396241
-
[Analysis of prevalence and variability of Legionella pneumophila and Legionella spp. strains on the basis of study of allelic profiles].Zh Mikrobiol Epidemiol Immunobiol. 2009 Nov-Dec;(6):17-21. Zh Mikrobiol Epidemiol Immunobiol. 2009. PMID: 20095417 Russian.
-
A meta-analysis of Legionella pneumophila contamination in hospital water systems.Am J Infect Control. 2023 Nov;51(11):1250-1262. doi: 10.1016/j.ajic.2023.04.002. Epub 2023 Apr 11. Am J Infect Control. 2023. PMID: 37054892
-
Confirming the Presence of Legionella pneumophila in Your Water System: A Review of Current Legionella Testing Methods.J AOAC Int. 2021 Aug 20;104(4):1135-1147. doi: 10.1093/jaoacint/qsab003. J AOAC Int. 2021. PMID: 33484265 Free PMC article. Review.
Cited by
-
Legionellosis Caused by Non-Legionella pneumophila Species, with a Focus on Legionella longbeachae.Microorganisms. 2021 Jan 31;9(2):291. doi: 10.3390/microorganisms9020291. Microorganisms. 2021. PMID: 33572638 Free PMC article. Review.
-
Dynamics of Legionella Community Interactions in Response to Temperature and Disinfection Treatment: 7 Years of Investigation.Microb Ecol. 2022 Feb;83(2):353-362. doi: 10.1007/s00248-021-01778-9. Epub 2021 Jun 5. Microb Ecol. 2022. PMID: 34091718 Free PMC article.
-
The Contribution of Legionella anisa to Legionella Contamination of Water in the Built Environment.Int J Environ Res Public Health. 2024 Aug 20;21(8):1101. doi: 10.3390/ijerph21081101. Int J Environ Res Public Health. 2024. PMID: 39200710 Free PMC article.
-
Legionella pneumophila in Municipal Shower Systems in Stavanger, Norway; A Longitudinal Surveillance Study Using Whole Genome Sequencing in Risk Management.Microorganisms. 2022 Feb 28;10(3):536. doi: 10.3390/microorganisms10030536. Microorganisms. 2022. PMID: 35336109 Free PMC article.