Computational Intelligence Powered Experimental Test on Energy Consumption Characteristics of Cold-Water Phase-Change Energy Heat Pump System
- PMID: 36110910
- PMCID: PMC9470346
- DOI: 10.1155/2022/1941855
Computational Intelligence Powered Experimental Test on Energy Consumption Characteristics of Cold-Water Phase-Change Energy Heat Pump System
Abstract
In order to study the influence on the effective energy efficiency ratio, the energy consumption characteristics of a cold-water phase change heat pump system are discussed in this article. An experimental system of the cold-water phase-change energy heat pump system is designed and constructed, and then the deicing energy consumption and unit energy consumption of the heat pump system are analyzed by computational intelligence-powered methods. At last, the primary energy utilization ratio of the heat pump system is calculated. The results show that under the setting conditions, the deicing capacity of the heat pump system is about 0.135, the primary energy utilization ratio is about 1.145, and the COP (coefficient of performance) of the heat pump unit is between 2.8 and 3.2. Considering the system's deicing energy consumption, the effective COP of the unit is between 2.42 and 2.76, so from this point, this kind of heat pump system can be widely used in the future. In order to improve the effective COP of the unit, the processes of ice making and melting should be further optimized to reduce heat loss and power loss.
Copyright © 2022 Ronghua Wu et al.
Conflict of interest statement
The authors declare no conflicts of interest.
Figures
References
-
- Gaur A. S., Fitiwi D. Z., Curtis J. Heat pumps and our low-carbon future: a comprehensive review. Energy Research & Social Science . 2021;71 doi: 10.1016/j.erss.2020.101764.101764 - DOI
-
- Shi Y. Heat Pump System Technology Scheme for Extracting Cold Water Solidification Heat . Modern Manufacturing Technology and Equipment; 2018.
-
- Jianfeng Q., Dexing S., Jili Z. A new heat pump technology with freezing heat collection and analysis of integrated heating performance. Journal of Dalian University of Technolgy . 2011;51(2):244–249.
-
- Jianfeng Q., Chenghu Z., Dexing S. Study on the freezing characteristics of water flow in a condenser heat collector. Heating Ventilating & Air Conditioning . 2007;37(3):5–9.
-
- Jianfeng Q. Form and Working Condition Analysis of Cold Water Phase Change Energy Heat Pump System . Harbin: Harbin Institute of Technology; 2008.
LinkOut - more resources
Full Text Sources