Containment of a Verona Integron-Encoded Metallo-Beta-Lactamase-Producing Pseudomonas aeruginosa Outbreak Associated With an Acute Care Hospital Sink-Tennessee, 2018-2020
- PMID: 37180588
- PMCID: PMC10173543
- DOI: 10.1093/ofid/ofad194
Containment of a Verona Integron-Encoded Metallo-Beta-Lactamase-Producing Pseudomonas aeruginosa Outbreak Associated With an Acute Care Hospital Sink-Tennessee, 2018-2020
Abstract
Background: Contaminated healthcare facility wastewater plumbing is recognized as a source of carbapenemase-producing organism transmission. In August 2019, the Tennessee Department of Health (TDH) identified a patient colonized with Verona integron-encoded metallo-beta-lactamase-producing carbapenem-resistant Pseudomonas aeruginosa (VIM-CRPA). A record review revealed that 33% (4 of 12) of all reported patients in Tennessee with VIM had history of prior admission to acute care hospital (ACH) A intensive care unit (ICU) Room X, prompting further investigation.
Methods: A case was defined as polymerase chain reaction detection of blaVIM in a patient with prior admission to ACH A from November 2017 to November 2020. The TDH performed point prevalence surveys, discharge screening, onsite observations, and environmental testing at ACH A. The VIM-CRPA isolates underwent whole-genome sequencing (WGS).
Results: In a screening of 44% (n = 11) of 25 patients admitted to Room X between January and June 2020, we identified 36% (n = 4) colonized with VIM-CRPA, resulting in 8 cases associated with Room X from March 2018 to June 2020. No additional cases were identified in 2 point-prevalence surveys of the ACH A ICU. Samples from the bathroom and handwashing sink drains in Room X grew VIM-CRPA; all available case and environmental isolates were found to be ST253 harboring blaVIM-1 and to be closely related by WGS. Transmission ended after implementation of intensive water management and infection control interventions.
Conclusions: A single ICU room's contaminated drains were associated with 8 VIM-CRPA cases over a 2-year period. This outbreak highlights the need to include wastewater plumbing in hospital water management plans to mitigate the risk of transmission of antibiotic-resistant organisms to patients.
Keywords: carbapenem-resistant; carbapenemase; healthcare-associated infections; opportunistic pathogens of premise plumbing; outbreak.
© The Author(s) 2023. Published by Oxford University Press on behalf of Infectious Diseases Society of America.
Conflict of interest statement
Potential conflicts of interest. All authors: No reported conflicts of interest.
Figures
References
-
- Centers for Disease Control and Prevention . CDC’s Antibiotic Resistance Threats in the United States, 2019. Available at: https://www.cdc.gov/drugresistance/biggest-threats.html. Accessed December 12, 2022.
-
- Centers for Disease Control and Prevention . Reduce Risk from Water. Available at: https://www.cdc.gov/hai/prevent/environment/water.html. Accessed December 23, 2022.
-
- Decraene V, Phan HTT, George R, et al. . A large, refractory nosocomial outbreak of Klebsiella pneumoniae carbapenemase-producing Escherichia coli demonstrates carbapenemase gene outbreaks involving sink sites require novel approaches to infection control. Antimicrob Agents Chemother 2018; 62:e01689–18. - PMC - PubMed
-
- Parkes LO, Hota SS. Sink-related outbreaks and mitigation strategies in healthcare facilities. Curr Infect Dis Rep 2018; 20:42. - PubMed
LinkOut - more resources
Full Text Sources
Miscellaneous