Skip to main page content
U.S. flag

An official website of the United States government

Dot gov

The .gov means it’s official.
Federal government websites often end in .gov or .mil. Before sharing sensitive information, make sure you’re on a federal government site.

Https

The site is secure.
The https:// ensures that you are connecting to the official website and that any information you provide is encrypted and transmitted securely.

Access keys NCBI Homepage MyNCBI Homepage Main Content Main Navigation
. 2024 May:147:115-122.
doi: 10.1016/j.jhin.2024.02.007. Epub 2024 Feb 27.

What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?

Affiliations
Free article

What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?

J L A Lans et al. J Hosp Infect. 2024 May.
Free article

Abstract

Background: The operating room (OR) department is one of the most energy-intensive departments of a hospital. The majority of ORs in the Netherlands have an air-handling installation with an ultra-clean ventilation system. However, not all surgeries require an ultra-clean OR.

Aim: To determine the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean ORs.

Methods: Lower air volume ventilation effectiveness (VELv) of conventional ventilation (CV), controlled dilution ventilation (cDV), temperature-controlled airflow (TcAF) and unidirectional airflow (UDAF) systems were evaluated within a 4 × 4 m measuring grid of 1 × 1 m. The VELv was defined as the recovery degree (RD), cleanliness recovery rate (CRR) and air change effectiveness (ACE).

Findings: The CV, cDVLv and TcAFLv ventilation systems showed a comparable mixing character in all areas (A, B and AB) when reducing the air change rate to 20/h. Ventilation effectiveness decreased when the air change rate was reduced, with the exception of the ACE. At all points for the UDAF-2Lv and at the centre point (C3) of the TcAFLv, higher RD10Lv and CRRLv were measured when compared with the other examined ventilation systems.

Conclusions: The ventilation effectiveness decreased when an ultra-clean OR with an ultra-clean ventilation air-supply system was switched to an air change rate of 20/h. Reducing the air change rate in the OR from an ultra-clean OR to a generic OR will reduce the recovery degree (RD10) by a factor of 10-100 and the local air change rate (CRR) by between 42% and 81%.

Keywords: Air change effectiveness; Cleanliness recovery rate; Operating room; Recovery degree; Ultra-clean ventilation systems; Ventilation effectiveness.

PubMed Disclaimer

Similar articles

Cited by

LinkOut - more resources