An evaluation of a partial-walled laminar-flow operating room
- PMID: 4529595
- PMCID: PMC2130548
- DOI: 10.1017/s0022172400023858
An evaluation of a partial-walled laminar-flow operating room
Abstract
This paper contains an assessment of the physical performance of a permanently installed down-flow laminar-flow operating room at the London Hospital. This system employs partial walls extending 0.76 m (2.5 ft.) from the ceiling, from which the air is allowed to issue freely downwards at an initial velocity of about 0.4 m./sec. (80 ft./min.).The usefulness of the partial wall, as compared with a free issuing system, was demonstrated and a comparison made with a fully walled system. It was shown that a fully walled system would be more efficient than a partial-walled system as there was a loss in air velocity of about 20-25% with the partial wall due to the nonconstrained flow of air. This loss would be reflected in an increase in airborne bacterial count and would mean that an increase of 20-25% in the air volume would be required to obtain the same conditions as with the full-walled system. Entrainment of contaminated air was demonstrated but it was concluded that this would be of little consequence in the centre of the clean area, i.e. at the wound site. Sterile instruments, etc., however, on the outside of the clean area, would be more liable to airborne contamination.Bacterial and dust airborne counts taken during total hip operations gave a very low average figure (0.3 bacteria/ft.(3) or 10.5/m.(3)) from which we conclude that the system was about 30 times cleaner in terms of airborne bacteria than a well ventilated conventional operating-room. We concluded that although the partial-walled system was slightly less efficacious than a normal full-walled system, the freedom of movement and of communication for the operating team could in some circumstances outweigh this disadvantage.Sound levels were such that normal conversation was possible with little or no awareness of background noise.
Similar articles
-
A bacteriological evaluation of laminar-flow systems for orthopaedic surgery.J Hyg (Lond). 1973 Sep;71(3):559-64. doi: 10.1017/s0022172400046544. J Hyg (Lond). 1973. PMID: 4518355 Free PMC article.
-
[Comparison of perforated metal ceiling systems (supported airflow ceilings) with laminar airflow ceilings in type A (DIN 1946 T.4) operating rooms under surgical conditions].Zentralbl Hyg Umweltmed. 1995 Oct;198(1):84-95. Zentralbl Hyg Umweltmed. 1995. PMID: 9409897 German.
-
[Hygienic Inspections of Ventilation Systems Under Resting Conditions (According to DIN 1946-4:1999-03) - A Retrospective Assessment].Zentralbl Chir. 2018 Dec;143(6):617-624. doi: 10.1055/s-0043-120916. Epub 2018 Jan 11. Zentralbl Chir. 2018. PMID: 29325198 German.
-
Laminar air-flow air conditioning in the operating room: a review.Anesth Analg. 1974 Mar-Apr;53(2):194-9. Anesth Analg. 1974. PMID: 4593089 Review. No abstract available.
-
The role of air ventilation and air sampling in reducing the incidence of surgical wound infection rates.Br J Theatre Nurs. 1996 Dec;6(9):29-32. Br J Theatre Nurs. 1996. PMID: 9052043 Review.
Cited by
-
Strategies for daily operating room management of ambulatory surgery centers following resolution of the acute phase of the COVID-19 pandemic.J Clin Anesth. 2020 Sep;64:109854. doi: 10.1016/j.jclinane.2020.109854. Epub 2020 Apr 29. J Clin Anesth. 2020. PMID: 32371331 Free PMC article.
-
Observing and quantifying airflows in the infection control of aerosol- and airborne-transmitted diseases: an overview of approaches.J Hosp Infect. 2011 Mar;77(3):213-22. doi: 10.1016/j.jhin.2010.09.037. Epub 2010 Dec 30. J Hosp Infect. 2011. PMID: 21194796 Free PMC article. Review.
-
Sepsis rates in hip replacement surgery with special reference to the use of ultra clean air.Arch Orthop Unfallchir. 1977 Nov 21;90(1):1-14. doi: 10.1007/BF00415890. Arch Orthop Unfallchir. 1977. PMID: 597086
References
MeSH terms
Substances
LinkOut - more resources
Full Text Sources