Protective isolation in single-bed rooms: studies in a modified hospital ward
- PMID: 5289715
- PMCID: PMC2131037
- DOI: 10.1017/s0022172400021793
Protective isolation in single-bed rooms: studies in a modified hospital ward
Abstract
Studies were made in a modified hospital ward containing 19 beds, 14 of them in the open ward, one in a window-ventilated side-room, two in rooms with partial-recirculation ventilators giving 7-10 air changes per hour, and two in self-contained isolation suites with plenum ventilation (20 air changes per hour), ultra-violet (UV) barriers at doorways and airlocks.Preliminary tests with aerosols of tracer bacteria showed that few bacteria entered the plenum or recirculation-ventilated rooms. Bacteria released inside mechanically ventilated cubicles escaped into the corridor, but this transfer was reduced by the presence of an airlock. UV barriers at the entrance to the airlock and the cubicle reduced the transfer of bacteria from cubicle to corridor.During a period of 4 years while the ward was in use for surgical and gynaecological patients, the incidence of post-operative sepsis and colonization of wounds by multiple-resistant Staphylococcus aureus was lower (though not significantly lower) in the plenum-ventilated rooms than in the open ward, the recirculator-ventilated cubicles and the window-ventilated cubicles. Nasal acquisition of multiple-resistant Staph. aureus was significantly less common in the plenum-ventilated than in the recirculator-ventilated cubicles and in the other areas. Mean counts of bacteria on settle-plates were significantly lower in the plenum-ventilated cubicles than in the other areas; mean settle-plate counts in the recirculator-ventilated cubicles were significantly lower than in the open ward and in the window-ventilated side-room; similar results were shown by slit-sampling of air. Mean settle-plate counts were significantly lower in all areas when the ward was occupied by female patients. Staph. aureus was rarely carried by air from plenum-ventilated or other cubicles to the open ward, or from the open ward to the cubicles; though staphylococci were transferred from one floor area to another, they did not appear to be redispersed into the air in sufficient numbers to infect the patients. Ultra-violet irradiation caused a significant reduction in the total and staphylococcal counts from the floors of airlocks, and a significant reduction of total counts in the air.
Similar articles
-
Protective isolation in a burns unit: the use of plastic isolators and air curtains.J Hyg (Lond). 1971 Dec;69(4):529-46. doi: 10.1017/s002217240002180x. J Hyg (Lond). 1971. PMID: 5002642 Free PMC article.
-
Nasal acquisition of Staphylococcus aureus in a subdivided and mechanically ventilated ward: endemic prevalence of a single staphylococcal strain.J Hyg (Lond). 1970 Sep;68(3):417-33. doi: 10.1017/s0022172400042327. J Hyg (Lond). 1970. PMID: 5272345 Free PMC article.
-
Wound infections after surgery in a modern operating suite: clinical, bacteriological and epidemiological findings.J Hyg (Lond). 1979 Aug;83(1):41-57. doi: 10.1017/s002217240002581x. J Hyg (Lond). 1979. PMID: 379212 Free PMC article.
-
The ventilation of multiple-bed hospital wards: review and analysis.Am J Infect Control. 2008 May;36(4):250-9. doi: 10.1016/j.ajic.2007.07.012. Am J Infect Control. 2008. PMID: 18455045 Review.
-
Are infection control measures helpful in reducing paediatric ward infections?Paediatr Child Health (Oxford). 2018 Jun;28(6):282-288. doi: 10.1016/j.paed.2018.04.004. Epub 2018 May 3. Paediatr Child Health (Oxford). 2018. PMID: 32288784 Free PMC article. Review.
Cited by
-
A unit for source and protective isolation in a general hospital.Br Med J. 1979 Aug 25;2(6188):461-5. doi: 10.1136/bmj.2.6188.461. Br Med J. 1979. PMID: 487003 Free PMC article.
-
Surveys of hospital infection in the Birmingham region. I. Effect of age, sex, length of stay and antibiotic use on nasal carriage of tetracycline-resistant Staphyloccus aureus and on post-operative wound infection.J Hyg (Lond). 1977 Oct;79(2):299-314. doi: 10.1017/s0022172400053110. J Hyg (Lond). 1977. PMID: 269204 Free PMC article.
-
Isolating patients in hospital to control infection. Part III--Design and construction of isolation accommodation.Br Med J. 1978 Sep 9;2(6139):744-8. doi: 10.1136/bmj.2.6139.744. Br Med J. 1978. PMID: 698706 Free PMC article. No abstract available.
-
Isolating patients in hospital to control infection. Part I--Sources and routes of infection.Br Med J. 1978 Aug 26;2(6137):609-13. doi: 10.1136/bmj.2.6137.609. Br Med J. 1978. PMID: 698615 Free PMC article. No abstract available.
-
Opportunistic infection.Br Med J. 1973 Apr 14;2(5858):107-10. doi: 10.1136/bmj.2.5858.107. Br Med J. 1973. PMID: 4633652 Free PMC article. No abstract available.
References
MeSH terms
LinkOut - more resources
Full Text Sources