Epidemic Legionnaires' disease. Airborne transmission down a chimney
- PMID: 7230470
Epidemic Legionnaires' disease. Airborne transmission down a chimney
Abstract
Between June 18 and July 9, 1979, Legionnaires' disease (LD) developed in 13 persons who had visited a hotel complex in Wisconsin. All had visited the part of the hotel that contains the restaurants and meeting rooms (building A). Legionnaires' disease occurred in 1% who had been exclusively in the meeting rooms and in 0.1% who had eaten only at the hotel restaurants. Furthermore, 1.5% exposed to meeting room 1 and none of those exposed only to the other meeting rooms had LD. Legionella pneumophila was isolated from water in the cooling tower on top of building A. Located within 5 m downwind of the cooling-tower exhaust, a chimney with an open damper allowed cooling-tower exhaust (as demonstrated by air tracer studies) to enter meeting room 1 via the fireplace. Although cases did not occur after the cooling-tower water was treated by continuous hyperchlorination and the chimney was sealed, a seven-day lag occurred between treatment and elimination of the organism from the tower water.
Similar articles
-
An outbreak of Legionnaires' disease associated with a contaminated air-conditioning cooling tower.N Engl J Med. 1980 Feb 14;302(7):365-70. doi: 10.1056/NEJM198002143020703. N Engl J Med. 1980. PMID: 7351928
-
Community-acquired Legionnaires' disease associated with a cooling tower: evidence for longer-distance transport of Legionella pneumophila.Am J Epidemiol. 1989 Sep;130(3):557-68. doi: 10.1093/oxfordjournals.aje.a115370. Am J Epidemiol. 1989. PMID: 2764000
-
Nosocomial Legionnaires' disease. Epidemiologic demonstration of cooling towers as a source.JAMA. 1985 Jul 26;254(4):521-4. doi: 10.1001/jama.254.4.521. JAMA. 1985. PMID: 4009880
-
Mode of transmission of Legionella pneumophila. A critical review.Arch Intern Med. 1986 Aug;146(8):1607-12. Arch Intern Med. 1986. PMID: 3524495 Review. No abstract available.
-
[Incidence and significance of Legionella in industrial air conditioning systems].Schriftenr Ver Wasser Boden Lufthyg. 1993;91:231-40. Schriftenr Ver Wasser Boden Lufthyg. 1993. PMID: 8235479 Review. German. No abstract available.
Cited by
-
An alkaline approach to treating cooling towers for control of Legionella pneumophila.Appl Environ Microbiol. 1987 Aug;53(8):1775-9. doi: 10.1128/aem.53.8.1775-1779.1987. Appl Environ Microbiol. 1987. PMID: 3662515 Free PMC article.
-
Effects of climate changes and road exposure on the rapidly rising legionellosis incidence rates in the United States.PLoS One. 2021 Apr 22;16(4):e0250364. doi: 10.1371/journal.pone.0250364. eCollection 2021. PLoS One. 2021. PMID: 33886659 Free PMC article.
-
Legionella oakridgensis: unusual new species isolated from cooling tower water.Appl Environ Microbiol. 1983 Feb;45(2):536-45. doi: 10.1128/aem.45.2.536-545.1983. Appl Environ Microbiol. 1983. PMID: 6830217 Free PMC article.
-
Failure of Legionella pneumophila sensitivities to predict culture results from disinfectant-treated air-conditioning cooling towers.Appl Environ Microbiol. 1982 Jan;43(1):240-4. doi: 10.1128/aem.43.1.240-244.1982. Appl Environ Microbiol. 1982. PMID: 7055374 Free PMC article.
-
Uses of inorganic hypochlorite (bleach) in health-care facilities.Clin Microbiol Rev. 1997 Oct;10(4):597-610. doi: 10.1128/CMR.10.4.597. Clin Microbiol Rev. 1997. PMID: 9336664 Free PMC article. Review.
Publication types
MeSH terms
LinkOut - more resources
Full Text Sources
Medical
Research Materials