The effect of a portable HEPA-filtered body exhaust system on airborne microbial contamination in a conventional operating room
- PMID: 8839798
- DOI: 10.1086/647332
The effect of a portable HEPA-filtered body exhaust system on airborne microbial contamination in a conventional operating room
Abstract
Objective: To study the effect of a portable HEPA-filtered air exhaust system (Stackhouse Freedom Surgical Helmet System) on airborne microbial contamination in a modern conventional operating room.
Design and setting: Microbial air sampling was done with a two-stage Anderson sampler at the wound site during 46 total joint replacements. All operations were performed by the same surgeon in the same operating room at a large community hospital.
Results: In 18 cases done without air exhaust hoods, the number of bacterial and fungal colony-forming units (CFU) ranged from 0.6 to 11.7 (mean, 3.6). Air sampling during 28 operations with the operating team in air exhaust hoods revealed a mean of 3.6 CFU (range, 0 to 11.4). Bacterial CFU averaged 3.4 without hoods and 3.2 with exhaust hoods. Coagulase-negative staphylococci were the most common isolates (48% of isolates with hood, 55% without hood). No infections occurred.
Conclusion: We concluded that these air exhaust hoods did not lower airborne microbial contamination detectable with this air sampling method, as compared to standard head cover and mask, in a modern conventional operating room.
Similar articles
-
Efficacy of the Steri-Shield filtered exhaust helmet in limiting bacterial counts in the operating room during total joint arthroplasty.J Arthroplasty. 1996 Jun;11(4):469-73. doi: 10.1016/s0883-5403(96)80038-6. J Arthroplasty. 1996. PMID: 8792255
-
Lack of influence of body exhaust gowns on aerobic bacterial surface counts in a mixed-ventilation operating theatre. A study of 62 hip arthroplasties.J Hosp Infect. 2003 May;54(1):2-9. doi: 10.1016/s0195-6701(03)00077-x. J Hosp Infect. 2003. PMID: 12767840
-
Environmental bacteriology in the unidirectional (vertical) operating room.Arch Surg. 1979 Jul;114(7):784-8. doi: 10.1001/archsurg.1979.01370310026006. Arch Surg. 1979. PMID: 454171
-
Environmental controls in operating theatres.J Hosp Infect. 2002 Jun;51(2):79-84. doi: 10.1053/jhin.2002.1217. J Hosp Infect. 2002. PMID: 12090793 Review.
-
Environment of care: Is it time to reassess microbial contamination of the operating room air as a risk factor for surgical site infection in total joint arthroplasty?Am J Infect Control. 2017 Nov 1;45(11):1267-1272. doi: 10.1016/j.ajic.2017.06.027. Epub 2017 Aug 14. Am J Infect Control. 2017. PMID: 28818359 Review.
Cited by
-
Intraoperative contamination and space suits: a potential mechanism.Eur J Orthop Surg Traumatol. 2014 Apr;24(3):409-13. doi: 10.1007/s00590-013-1178-1. Epub 2013 Feb 9. Eur J Orthop Surg Traumatol. 2014. PMID: 23412319
-
Surgeon Personal Protection: An Underappreciated Benefit of Positive-pressure Exhaust Suits.Clin Orthop Relat Res. 2018 Jun;476(6):1341-1348. doi: 10.1007/s11999.0000000000000253. Clin Orthop Relat Res. 2018. PMID: 29481350 Free PMC article.
-
Contamination Relative to the Activation Timing of Filtered-Exhaust Helmets.J Arthroplasty. 2016 Apr;31(4):776-80. doi: 10.1016/j.arth.2015.10.039. Epub 2015 Nov 10. J Arthroplasty. 2016. PMID: 26684270 Free PMC article.
-
The Gown-glove Interface Is a Source of Contamination: A Comparative Study.Clin Orthop Relat Res. 2015 Jul;473(7):2291-7. doi: 10.1007/s11999-014-4094-8. Clin Orthop Relat Res. 2015. PMID: 25488405 Free PMC article.
-
Does modern space suit reduce intraoperative contamination in total joint replacement? An experimental study.Eur J Orthop Surg Traumatol. 2017 Dec;27(8):1139-1143. doi: 10.1007/s00590-016-1874-8. Epub 2016 Oct 31. Eur J Orthop Surg Traumatol. 2017. PMID: 27796583