Zoned vertical ultraclean operating room ventilation. A novel concept making long side walls unnecessary
- PMID: 9065071
- DOI: 10.3109/17453679608997760
Zoned vertical ultraclean operating room ventilation. A novel concept making long side walls unnecessary
Abstract
We evaluated a novel concept of High Efficiency Particulate Air (HEPA)-filtered vertical Laminar Air Flow (LAF) for operating room ventilation, designed to be used without side-walls. The LAF-unit has a central zone with an airflow of 0.4 m/s and a peripheral zone with an airflow of 0.2 m/s. The design provides an exponential downflow of air resembling an upside-down trumpet mouth and it was claimed to prevent entrainment of peripheral contaminated air. The unit was evaluated with regard to elimination of particles with focus on bacteria-carrying particles (colony-forming units = cfu) during rigidly standardized sham operations. Three different lengths of walls/enclosures (short-ending 2.0 m, medium 1.0 m and long 0.2 m above the floor) were tested. It provided a high degree of bacteriological cleanliness (0.05-4 cfu/m3 of air and 7-64 cfu/m2/h surface contamination) and its efficiency was proved to be independent of the length of the enclosures. We conclude that the novel zoned ultraclean vertical LAF unit is versatile, as it allows for omitting long side-walls, without compromising bacteriological safety.
Similar articles
-
Zoned exponential, vertical and horizontal ultra-clean laminar airflows. No differences in bacteriological efficiency.Acta Orthop Scand. 1998 Apr;69(2):169-72. doi: 10.3109/17453679809117621. Acta Orthop Scand. 1998. PMID: 9602777
-
Ultraclean laminar airflow ORs.AORN J. 1998 Apr;67(4):841-2, 845-51. doi: 10.1016/s0001-2092(06)62647-1. AORN J. 1998. PMID: 9561276
-
Inconsistent correlation between aerobic bacterial surface and air counts in operating rooms with ultra clean laminar air flows: proposal of a new bacteriological standard for surface contamination.J Hosp Infect. 1999 Aug;42(4):287-93. doi: 10.1053/jhin.1998.0598. J Hosp Infect. 1999. PMID: 10467542
-
Laminar airflow and the prevention of surgical site infection. More harm than good?Surgeon. 2015 Feb;13(1):52-8. doi: 10.1016/j.surge.2014.10.003. Epub 2014 Nov 7. Surgeon. 2015. PMID: 25453272 Review.
-
Ultraclean air for prevention of postoperative infection after posterior spinal fusion with instrumentation: a comparison between surgeries performed with and without a vertical exponential filtered air-flow system.Spine (Phila Pa 1976). 2004 Oct 15;29(20):2330-4. doi: 10.1097/01.brs.0000142436.14735.53. Spine (Phila Pa 1976). 2004. PMID: 15480149 Review.
Cited by
-
Mobile ultra-clean unidirectional airflow screen reduces air contamination in a simulated setting for intra-vitreal injection.Int Ophthalmol. 2017 Feb;37(1):131-137. doi: 10.1007/s10792-016-0236-1. Epub 2016 Apr 30. Int Ophthalmol. 2017. PMID: 27138593 Free PMC article.
-
Use of an ultra-clean air flow for surgical field asepsis when performing intravitreous injections in an ambulatory surgical environment.Int J Retina Vitreous. 2020 Nov 19;6(1):57. doi: 10.1186/s40942-020-00258-5. Int J Retina Vitreous. 2020. PMID: 33292734 Free PMC article.
Publication types
MeSH terms
LinkOut - more resources
Other Literature Sources